Par.
Descripción
5.16 SCHEDULE PROGRAM 1
5.17 PROGRAM START TIME 1
5.18 PROGRAM STOP TIME 1
5.19 SCHEDULE PROGRAM 2
5.20 PROGRAM START TIME 2
5.21 PROGRAM STOP TIME 2
LOW WATER LEVEL ALARM
5.22
ACTIVE
LOW WATER LEVEL ALARM
5.23
DELAY
5.24 BURST PIPE ALARM
5.25 VOLTAGE ALARM ACTIVE
5.26 PARAMETER LOCK
5.27 SET DATE AND TIME
STOP FREQUENCY SEARCH
5.28
WIZARD
5.29 FACTORY SETTINGS
Programación
Ud.
Defecto
Min.
Max.
OFF
M-Su
OFF
M-F
Sa-Su
M ..... Su
00:00
00:00
23:59
00:00
00:00
23:59
OFF
Sa-Su
M-Su
M ..... Su
OFF
M-F
00:00
00:00
23:59
00:00
00:00
23:59
YES
YES
NO
Sec
5
1
99
YES
YES
NO
YES
YES
NO
NO
NO
YES
NO
NO
YES
NO
NO
YES
NO
NO
YES
19
Notas
In this parameter you can choose not to have a
schedule program (OFF) or the days of the week that
you want this program to run. You can choose between
whole weeks (M-Su), weekdays (M-F), weekends (Sa-
Su) or individual days.
The schedule program will act on the output relay
programmed for this purpose.
Start time of schedule program 1.
Stop time of schedule program 1.
Like parameter 5.16 but for a second schedule program.
Start time of schedule program 2.
Stop time of schedule program 2.
Parameter for enabling or disabling the low water
level alarm.
In the case of being active and cause notice, the
drive will start attempts by the following sequence:
5 minutes, 15 minutes, 1 hour, 6 hours or 24 hours.
The display shows the remaining time start attempt.
Pressing F2 we force the reset of the notice, still
unfinished countdown.
If after the 24-hour notice is detected again dry
running, the drive will lock indefinitely until you
press F2.
Time from when the system calculates a low water level
until the moment the alarm is activated for this reason.
Parameter for enabling or disabling the burst pipe
alarm.
Parameter for enabling or disabling the alarm due to
a power cut.
YES: Editing the values of the parameters is locked.
NO: Editing the values of the parameters is locked.
To change this parameter from YES to NO, you must
previously enter the password 1357.
When you change this parameters to "SI" this screen for
editing the date and time will appear. Once editing is
completed, the parameter returns to "NO".
If you change this parameter from "NO" to "YES" the
stop frequency search wizard will be launched.
To reset the unit and leave it with the factory settings,
change this parameter to "YES" and after you have entered
the code 1357 the unit will launch the start-up wizard.