Diagnostic Parameters - CARLO GAVAZZI IO-Link PD30CTB Serie Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 129

7.2.7. Diagnostic parameters

Index Dec
Parameter Name
Sensor Diagnostics
Frontend Failure
209 (0xD1)
EE_MemoryFailure (during
208 (0xD0)
power up)
Memory Failure
1 (0x01)
Temperature Diagnostics
Maximum temperature
203 (0xCB)
– All time high
Minimum temperature
204 (0xCC)
- All time low
Maximum temperature since
205 (0xCD)
power-up
Minimum temperature since
206 (0xCE)
power-up
Current temperature
207 (0xCF)
Minutes above Maximum
211 (0xD3)
Temperature
Minutes below Minimum
212 (0xD4)
Temperature
Operating Diagnostics
Operating Hours
201 (0xC9)
Number of Power Cycles
202 (0xCA)
Detection counter SSC1
210 (0xD2)
Maintenance event counter
213 (0xD5)
Download counter
214 (0xD6)
Quality of Teach
75 (0x4B)
Quality of Run
76 (0x4C)
Excess Gain
83 (0x53)
Error Count
32 (0x20)
Device Status
36 (0x24)
Detailed Device Status
37 (0x25)
Temperature fault
-
Temperature over-run
-
Temperature under-run
-
Short-circuit
-
Maintenance Required
-
Event Configuration
Event Configuration
74 (0x4A)
Maintenance event (0x8C30)
1 (0x01)
Temperature fault event
2 (0x02)
(0x4000)
Temperature over-run event
3 (0x03)
(0x4210)
Temperature under-run event
4 (0x04)
(0x4220)
Short circuit event (0x7710)
5 (0x05)
Access
Default value
(Hex)
RO
-
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
0 = Device is operating properly
-
RO
RO
RO
RO
RO
-
R/W
0 = Maintanance event Inactive
0 = Temperature fault
R/W
event Inactive
0 = Temperature over-run
R/W
event Inactive
0 = Temperature under-run
R/W
event Inactive
0 = Short circuit
R/W
event Inactive
Data range
0 = OK
0 = OK. 1 = Fail.
-
0 = OK
0 = OK. 1 = Fail.
- °C
-50 ... 150 [°C]
- °C
-50 ... 150 [°C]
- °C
-50 ... 150 [°C]
- °C
-50 ... 150 [°C]
- °C
-50 ... 150 [°C]
0 min
0 ... 2 147 483 647 [min]
0 min
0 ... 2 147 483 647 [min]
0 h
0 ... 2 147 483 647 [h]
0
0 ... 2 147 483 647
0
0 ... 2 147 483 647
0
0 ... 2 147 483 647
0
0 ... 65 536
-
0 ... 255
-
0 ... 255
-
1 ... 255%
0
0 ... 65 535
0 = Device is operating properly
1 = Maintenance required
2 = Out-of-specification
3 = Functional-Check
4 = Failure
-
-
-
-
-
-
-
0 = Maintenance event Inactive
1 = Maintenance event Active
0 = Temperature fault event Inactive
1 = Temperature fault event Active
0 = Temperature over-run event Inactive
1 = Temperature over-run event Active
0 = Temperature under-run event Inactive
1 = Temperature under-run event Active
0 = Short circuit event Inactive
1 = Short circuit event Active
Rev.00 - 06 .2021 | MAN PD30CTB IO-Link EN | © 2021 | CARLO GAVAZZI Industri
Data Type
IntegerT
-
-
IntegerT
IntegerT
IntegerT
IntegerT
IntegerT
IntegerT
IntegerT
IntegerT
IntegerT
IntegerT
IntegerT
IntegerT
UIntegerT
UIntegerT
UIntegerT
UIntegerT
UIntegerT
UIntegerT
-
-
-
OctetStringT
-
OctetStringT
-
OctetStringT
-
OctetStringT
-
OctetStringT
-
-
RecordT
RecordT
RecordT
RecordT
RecordT
Length
8 bit
-
8 bit
16 bit
16 bit
16 bit
16 bit
16 bit
32 bit
32 bit
32 bit
32 bit
32 bit
32 bit
16 bit
8 bit
8 bit
8 bit
16 Bit
8 Bit
-
3 Byte
3 Byte
3 Byte
3 Byte
3 Byte
-
16 bit
16 bit
16 bit
16 bit
16 bit
43