1. GENERAL

This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the
indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
The installation of pipe-work shall be kept to a minimum.
This symbol shows that this equipment uses a flammable refrigerant. If the refrigerant is leaked, together with
WARNING
an external ignition source, there is a possibility of ignition.
CAUTION
This symbol shows type of flammable refrigerant contained in the system.
This symbol shows that the Operating Instructions should be read carefully.
CAUTION
This symbol shows that a service personnel should be handling this equipment with reference to the Technical
CAUTION
Manual.
This symbol shows that there is information included in the Operating Instructions and/or Installation
CAUTION
Instructions.

1-1. Tools Required for Installation (not supplied)

1.
Flathead screwdriver
2.
Phillips head screwdriver
3.
Knife or wire stripper
4.
Tape measure
5.
Carpenter's level
6.
Sabre saw or keyhole saw
7.
Hacksaw
8.
Core bits
9.
Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)

1-2. Accessories Supplied with Unit

Table 1-1 (Low Silhouette Ducted)
Part Name
Figure
Washer
Flare insulator
Insulating
tape
Drain
insulator
Hose band
Packing
Packing
Drain hose
Q'ty
Remarks
For suspending indoor
8
unit from ceiling
2
For gas and liquid tubes
For gas and liquid tubes
2
flare nuts
1
For drain hose joint
1
For securing drain hose
For drain hose joint
1
(hard material)
For drain hose joint
1
(soft material)
1
Part Name
Figure
Operating
Instructions
Installation
Instructions
Short-circuit
connection
● Use M10 for suspension bolts.
● Suspension bolts and nuts are field supply.

1-3. Type of Copper Tube and Insulation Material

If you wish to purchase these materials separately from a local
source, you will need:
1.
Deoxidized annealed copper tube for refrigerant tubing.
2.
Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of the
insulation should be not less than 8 mm.
3.
Use insulated copper wire for field wiring. Wire size
varies with the total length of wiring. See the section
"4. ELECTRICAL WIRING" for details.
CAUTION
Check local electrical codes and regulations before
obtaining wire. Also, check any specified instructions or
limitations.

1-4. Additional Materials Required for Installation

1.
Refrigeration (armored) tape
2.
Insulated staples or clamps for connecting wire (See your
local codes.)
3.
Putty
4.
Refrigeration tubing lubricant
5.
Clamps or saddles to secure refrigerant tubing
6.
Scale for weighing
7
Q'ty
Remarks
1
1
For high static pressure
(Located on the back of
1
the electrical component
box lid. )