Step-by-step installation instructions
Step 1: Mounting
Note: Mount the T-Series ESN unit where it can be easily located
and accessed if servicing or troubleshooting is necessary.
• For indoor use only.
• NEMA, Type 1 enclosure, IP20.
• Remove metal outer panel cover.
• Remove internal plastic line voltage shield.
• Choose panel mounting location so line voltage wiring is at least
6 ft (1.8 m) from audio or electronic equipment and associated
wiring (prevents radio frequency interference).
• Install in accordance with all national and local electrical codes.
• Complies with requirements for use in other spaces used for
environmental air (plenums) per NECR 2014 300.22(C)(3)
Step 2: Control power wiring
The T-Series ESN unit operates at 120–277 V~. Use the following
instructions to wire line voltage to the T-Series ESN unit.
WARNING: Shock Hazard. May result in serious injury
or death. Do not wire when live. Turn off power to all
power feeds via circuit breaker or isolator before wiring or
servicing.
Buttons and LEDs in the unit are used for troubleshooting. If
wiring is exposed when accessing buttons and LEDs, the unit
must be accessed by a certified electrician, following local
codes.
1. Turn power off.
2. Remove metal outer panel cover.
3. Remove internal plastic line voltage shield.
4. Use 14 AWG to 12 AWG (2.5 mm
(depending on breaker rating) to feed the control power wiring.
The device draws less than 0.5 A.
5. Wire the line voltage cables to the terminals labeled H/L (Hot/Line),
N (Neutral) and
(Ground).
6. Reinstall internal plastic line voltage shield.
7. Turn on the circuit breaker or isolator to power up the T-Series
ESN unit. The Power LED on the T-Series ESN unit will illuminate
continuously when properly energized. If the LED does not light,
turn off power, then check the control power wiring.
8. Turn power off.
T-Series Energi Savr Node
to 4.0 mm
) conductors
2
2
Installation Guide
T-Series Energi Savr Node

Mechanical Dimensions

All dimensions shown as: in (mm)
(234.95)
Line Voltage Shield

Control Power Wiring

H/L
N
LOOP 2
LOOP 1
PWR
TEST
TEST
TEMP
QS LINK
GROUP 1
• Two (2) 14 AWG to 12 AWG (2.5 mm
• Strip length: 3/8 in (8.5 mm)
• Torque: 7 in-lb (0.79 N
English
Español
|
Installation Guide
9.25
1.31
1.66
(33.27)
(42.16)
1.22
(30.99)
0.88
7.50
(22.35)
(190.50)
1.00
(25.40)
11.25
(285.75)
0.20
(5.16) dia.
N/C
LOOP 2
LOOP 1
RESET
H/L
GROUP 2
GROUP 3
GROUP 4
CONTACT CLOSURE
ETHERNET
to 4.0 mm
2
m)
LOOP 2
LOOP 1
PWR
TEST
TEST
TEMP
QS LINK
GROUP 1
Français
3.16
(80.26)
1.22
(30.99)
Do not use
knockouts located
in this area on
either side of the
enclosure.
13.25
(336.55)
Do not use
(N/C)
N
N/C
)
2
Lutron
|
GROUP 2
GROUP 3
GROUP 4
3
CONTAC

Publicidad

loading