Index: 0
0 cm
Index: 1 xxx.x cm xxxx L
Index: 2
. cm
Index: 3
. cm
max.
Index:16 max. cm max. L
Not all 15 intermediate value pairs (Index: 1 - 15) have to be entered.
A linear interpolation is made between 2 interpolation values. For a linear range of the tank
geometry it is sufficient to enter a lower and an upper value pair.
Menu
Input function
Adjust the tank volume with [+] / [-] (100%). The default
4.Tank
setting is 0 L. The value must be set.
volume
Enter inner tank height in millimetres: e. g.: 249 cm
5.Tank
(max. value = 999,9 cm) (height without dome)
height
Set the filling limit of the tank with [+]/ [-]:
5b.Filling
With fuel oil tanks, that is the shut-off point of the limit
limit
indicator. The default setting is 95%.
e.g. 95%=237cm. For tanks which can be filled to the
very top (e.g. water tanks), it is necessary to set the
highest value of 99%.
In the 1st line of the display, the tank name/medium and
6.View
contents are displayed (e.g. in litres).
Tank
The display in the 2nd line can be selected:
SmartBox 4
View details
e.g.
Single/detailed
For fuel oil tanks in Germany, a free capacity display is
required according to TRwS 791-2. This is possible with
selection a) and b).
Steps 7 is only required for SmartBox
Entering incorrect switching points and mixing up the switch-on and shut-off
point can lead to the overfilling of the tank or the dry running of a pump!
Menu
7.Relay 2
SmartBox 2
or
7.Relay
SmartBox 3
26 / 112
0 L
Specified value pair (do not have to be entered).
first value pair entered
L
L
max. inside height of tank the max. tank volume
menu step "5.Internal tank height" is allocated
automatically and does not have to be entered.
Please see a volume table for the highest value,
if available. For a 100 m³ cyl. buried tank, this
may for example be the value 100600 litres.
Please see a volume table for the highest value,
if available. For a 100 m³ cyl. buried tank, this
may for example be the value 288 cm.
Input function
See 7. Relay 1 for the data for Relay 2 (or Relay)
®
SmartBox
1 / SmartBox
Fillspace+Percent
Fillspace+Level
Percent+Level
®
2 and SmartBox
®
2 / SmartBox
Input value
___________L
_________mm
__________%
____________
a)
b)
c)
®
3
Input value
on ______%
off ______%
on ______°C
off ______°C
Artikel-Nr. 28 100 51 h
®