Para el "Timeout de la trama de recepción" se aplican los siguientes tiempos
BAUD = 115200:
Receive_Conditions.END.RCVTIME := 25;
Receive_Conditions.END.MSGTIME := 25;
ELSIF BAUD = 57600 THEN
Receive_Conditions.END.RCVTIME := 29;
Receive_Conditions.END.MSGTIME := 29;
ELSIF BAUD = 38400 THEN
Receive_Conditions.END.RCVTIME := 33;
Receive_Conditions.END.MSGTIME := 33;
ELSIF BAUD = 19200 THEN
Receive_Conditions.END.RCVTIME := 56;
Receive_Conditions.END.MSGTIME := 56;
ELSIF BAUD = 9600 THEN
Receive_Conditions.END.RCVTIME := 72;
Receive_Conditions.END.MSGTIME := 72;
ELSIF BAUD = 4800 THEN
Receive_Conditions.END.RCVTIME := 100;
Receive_Conditions.END.MSGTIME := 124;
ELSIF BAUD = 2400 THEN
Receive_Conditions.END.RCVTIME := 100;
Receive_Conditions.END.MSGTIME := 240;
ELSIF BAUD = 1200 THEN
Receive_Conditions.END.RCVTIME := 100;
Ejemplo:
5 accionamientos
Velocidad de transferencia = 9600 bits/s
28 caracteres por trama
Tiempo de ciclo = 0,020 s
Intervalo = (5 * 5 * 0,02 s + 2 * 28 * 11 / 1200 s) * 3 = 1,69 s
En este caso, la vigilancia de tiempo del accionamiento debe ajustarse aprox. a 2 segundos.