The Ducted Split Type Air-Conditioning Units(Inverter Series) Installation and Operation Manual

2.6.1 Connection of Wire and Patch Board Terminal

(1) The connection of wire (as shown in fig.13)
1) Strip about 25mm (1 in.) insulation of the wire end by stripping and cutting tool.
2) Remove the wiring screws on the terminal board.
3) Shape the tail of wire into ring by needle nose plier, and keep the gauge of ring in
accordance with screw.
4) Use the screwdriver for tightening the terminal.
(2) The connection of stranded wire (as shown in fig.14)
1) Strip about 10mm (3/8 in.) insulation of the end of stranded wire by stripping and
cutting tool.
2) Loosen the wiring screws on terminal board.
3) Insert the wire into the ring tongue terminal and tighten by crimping tool.
4) Use the screwdriver for tightening the terminal.

2.6.2 Connect Communication Wire of Wired Controller

(1) Open electric box cover of indoor unit.
(2) Let the communication wire go through the rubber ring.
(3) Connect the communication wire to terminal H1 and H2 of indoor 4-bit wiring board.
(4) Fix the communication wire with wire clip on the electric box.
(5) Wiring instructions of remote receiving light board and wired controller:
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Fig.13
Fig.15
8
Fig.14