The PS power supply with device category 2G may be
used in zone 1 hazardous areas.
Installation
Danger
It is possible that sparks or impermissibly high surface
temperatures may occur during the installation. Never
perform an installation under explosive conditions!
In making the installation, observe the EN 60 079-14
regulations.
The PS power supply must be mounted in Zone 1 in an
enclosure with the Ex e degree of protection.
In Zone 2, the PS power supply must be mounted in an
enclosure providing a degree of protection of at least IP 54
(must have manufacturer's statement for Zone 2).
Wiring the TM-PS-A/TM-PS-B terminal submodule
When laying the cable and connecting the submodule,
observe the regulations in EN 60 079-14 plus any
applicable national regulations.
A5E00688978-05
II 2 G and I M2
Ex de [ib] IIC T4; Ex de [ib] I
KEMA 04 ATEX2263
IECEx KEM 05.0004
08/UL-BRCO-0004X