Switch-selectable voltage, SPDT
Select the voltage by placing the voltage jumper over the pins as illustrated below.
AC or DC version, SPDT, fail-safe
alarm
output
Page EN-12
SITRANS LPS200 – OPERATING INSTRUCTIONS
lamp
protective earth
terminal
signal output
or:
signal
L
N
output
or:
+
N
L
115 V AC, 50 to 60 Hz, 4 VA
230 V AC, 50 Hz, 6 VA
+
24 V DC, 2.5 W
All voltages ± 15 %
Switching and timing behaviour:
If the vane is not covered, the
rotating vane shaft will send
pulses at 20 second intervals. In
case of fault, the pulses are
missed. After 30 seconds, the
alarm relay will open.
24 V or 48 V or 115 V or 230 V AC,
PE
50/60 Hz, 5 VA
24 V DC, 2.5 W
PE
All voltages ± 15 %
voltage
jumper
A5E34210883