To set the facility mode ..........12 Daikin website (publicly accessible). Standby electricity saving function ..........13 ▪ The full set of latest technical data is available on the Daikin 9.2.1 About the standby electricity saving function ....13 Business Portal (authentication required).
Página 6
2 Specific installer safety instructions Installation site (see "4.1 Preparing the installation site" [ 4 7]) Charging refrigerant (see "6 Charging refrigerant" [ 4 10]) CAUTION WARNING ▪ Check if the installation location can support the unit's The refrigerant inside the unit is mildly flammable, but weight.
3 About the box WARNING About the box ALWAYS use multicore cable for power supply cables. Outdoor unit WARNING Use an all-pole disconnection type breaker with at least 3 mm between the contact point gaps that provide full 3.1.1 To remove the accessories from the disconnection under overvoltage category III.
4 Unit installation It is recommended to install a baffle plate when the air outlet is Prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field exposed to wind. supply). It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind.
5 Piping installation What? Distance Minimum allowable pipe length 1.5 m Maximum allowable height difference 15 m Connecting the refrigerant piping Drain port Bottom frame DANGER: RISK OF BURNING/SCALDING Drain plug Hose (field supply) CAUTION ▪ No brazing or welding on site for units with R32 Piping installation refrigerant charge during shipment.
6 Charging refrigerant Refrigerant type: R32 Checking the refrigerant piping Global warming potential (GWP) value: 675 5.3.1 To check for leaks WARNING: MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable. NOTICE Do NOT exceed the unit's maximum working pressure (see WARNING "PS High"...
7 Electrical installation To charge additional refrigerant WARNING ALWAYS use multicore cable for power supply cables. WARNING WARNING ▪ Only use R32 as refrigerant. Other substances may cause explosions and accidents. Use an all-pole disconnection type breaker with at least 3 ...
8 Finishing the outdoor unit installation Specifications of standard wiring Finishing the outdoor unit components installation Component Class 20 Class 25+35 To finish the outdoor unit Power supply cable Voltage 220~240 V installation Phase DANGER: RISK OF ELECTROCUTION Frequency 50 Hz Wire sizes 3-core cable ▪...
Daikin website (publicly accessible). Prerequisite: Test run may be performed in cooling or heating mode. ▪ The full set of latest technical data is available on the Daikin Prerequisite: Test run should be performed in accordance with the Business Portal (authentication required).
Página 15
13 Technical data Symbol Meaning Symbol Meaning H*P, LED*, V*L Pilot lamp, light emitting diode Terminal Light emitting diode (service Terminal strip (block) monitor green) Electronic expansion valve coil HIGH VOLTAGE High voltage Y*R, Y*S Reversing solenoid valve coil Intelligent eye sensor Ferrite core IPM* Intelligent power module...
Página 16
DAIKIN ISITMA VE SOĞUTMA SİSTEMLERİ SAN.TİC. A.Ş. Gülsuyu Mahallesi, Fevzi Çakmak Caddesi, Burçak Sokak, No:20, 34848 Maltepe İSTANBUL / TÜRKİYE Tel: 0216 453 27 00 Faks: 0216 671 06 00 Çağrı Merkezi: 444 999 0 Web: www.daikin.com.tr 3P650253-1 2021.02 Verantwortung für Energie und Umwelt...