Description and Installation Procedure
LED Driver with constant output voltage to run LED and 1-10V control input
(Electronic switching power supply with 1-10V control)
TYPE: 470539, 470540
1. Technical Data
Art.-No.:
Rated voltage
Constant output voltage
Output current
Max. 1,67A per channel
Partial load range
Protection Class
Control inputs 1-10V
No-load security
Short circuit- and overload protection
Ambient temperature ta
Case temperature tc-point
Excess temperature disconnection
automatical disconnection through self-contained temperature switch
EMV conformity
Standards
Primary wire
Secondary wire
Control wire 1-10V
Diameter of wires
Wire preparation
2. Important Information
!!Before switching on the supply voltage all LED must be completely wired
and connected!!
The installation may only be carried out by an electrical specialist in accordance with international
and national standards.
When working on electrical systems, the protection against electric shock is to be ensured by
disconnecting the system. Connecting under tension may destroy the LED.
The LED Driver is only intended for the use with LED that require a constant voltage of 12VDC or
24VDC.
Install primary and secondary mains intersection-free (RFI protection).
When connecting the LED, careful attention should be paid to connecting + and – to the right
terminals on LED Driver.
LED Drivers mounted outside of luminaires are to be screwed tightly to the respective surface by their screw
holes and careful attention is to be paid to the connecting cables and the lamp cables being fastened
securely in the strain relief.
The tc temperature may not be exceeded for any kind of mounting. The devices do not contain serviceable
components and may not be opened.
Protection class 1
CE
470539
470540
LPC60W12V3C
LPC100W24V3C
220-240V 0/50-60Hz
12VDC SELV
24VDC SELV
Max. 1,4 A pro per channel
0 - 20W per channel
0 - 33W per channel
I
3 channels
guaranteed
automatical disconnection through self-contained
temperature switch
-20°C - +50°C
60°C
70°C
EN 61547, EN 55015, EN 61000-3-2, EN 61000-3-3
EN 61347-1, EN 61347-2-13, EN 62384
min. H03VV-F 3x0,75mm², for strain relief
min. H03VV-F 4x0,5mm², for strain relief
min. H03VV-F 4x0,5mm², for strain relief
0,5 – 1,5mm², AWG 20-16
9mm
3. Important Information
Our LED Drivers are surge-voltage-stable up to values far above those prescribed by the respective
standards. As a protection against high voltage surges, as they occur e.g. when switching fluorescent lamps
and discharge lamps with an inductive ballast, motors (fans, etc.) and other inductive loads, the load circuits
for devices of this kind are to be clearly separated from each other.
4. Safety Function
In case of short circuit the LED Driver will automatically cut off. It does not have a fuse of the conventional
kind. Thus the load circuit is not separated!
Attention: Disconnect mains tension before working on the lighting installation!!!
As soon as the defect has been repaired, the LED Driver will automatically cut back in.
5. Excess Temperature
In case of excess temperature through external heat sources the built-in temperature switch will disconnect
the LED driver from the mains. As soon as the LED Driver has cooled off, it will automatically cut back in.
6. Heat Dissipation and Heat Transfer
Operation in excess ambient temperature or through external heating will reduce the service life. During the
installation process ( particularly into luminaires ), heat dissipation ( heat transfer ) is to be provided through
suitable measures. The ambient temperature and/or the tc-point temperature may not be exceeded at any
time. We are not liable for damage resulting from improper use.
7. 1-10V Control inputs
An extern control can be connected to the 1-10V control inputs to control the 3 PWM-channels.
Art.-No. 470539/470540
07/2011
SLV Elektronik GmbH, Daimlerstr. 21-23, 52531 Übach-Palenberg,
Germany, Tel. +49 (0)2451 4833-0