Outdoor Unit
Liquid Valve
FOR SL 30 / 40 / 50 / 60 C/CR & 4SL 30 / 40 / 50 / 60 C/CR:
The refrigerant is pre-charged in the outdoor unit. If the piping
length is less than 7.6 m, additional charge after vacuuming is not
necessary. When the piping length is more than 7.6 m, use the
table below.
Additional Charge Operation
This operation must be done by using gas cylinder and a precise
weighing machine obligatorily. The additional charge is top up
into the outdoor unit by suction valve via service port.
• Remove the service valve plug.
• Connect the low pressure manifold to the suction service port,
center manifold to the cylinder tank and close the high pressure
manifold (see figure below).
Purge all the flexible hose with refrigerant gas.
• Start the air conditioner unit.
• Open the gas cylinder and low pressure manifold valve.
• When the required refrigerant quantity is pumped in the unit,
close the low pressure manifold and the gas cylinder valve.
• Disconnect the manometer and the gas cylinder. Place back the
service port cap.
Outdoor Unit
Liquid Valve
Refrigerant Piping
Low Side
Pressure Gauge
Gas Valve
Manifold

ADDITIONAL CHARGE

Refrigerant Piping
Low Side
Pressure Gauge
Gas Valve
Manifold
1-11
Indoor Unit
High Pressure Gauge
Flexible Hose
Vacuum Pump
Additional Charge in Gram (Cooling Unit R22 & R407C)
Model
10 m 15 m 20 m 25 m 30 m 35 m
CC30D/40D/50D
120
CC60D
230
Additional Charge in Gram (Heat Pump Unit R22 &
R407C)
Model
10 m 15 m 20 m 25 m 30 m 35 m
CC30DR/40DR/50DR 90
CC60DR
160
Additional Charge in Gram (Cooling and Heat Pump
Unit R410A)
Model
10 m 15 m 20 m 25 m 30 m 35 m
5CC30D/40D/50D/60D/DR
70
Check Refrigerant Leak
Check with refrigerant detector whether there is a leak on the flare
type connection of the indoor unit and outdoor unit.
Hints: After operation for sometime, check if there is oil traces,
there is a leak.
Indoor Unit
High Pressure Gauge
Flexible Hose
Refrigerant Gas Tank
370
620
870 1120 1370
700 1180 1650 2120 2600
270
440
620
800 980
500
840 1180 1520 1850
220
370
510
660 810