Tripp-Lite BP240V65 Manual Del Propietário página 64

Gabinete de baterías para autonomía extendida
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6. Operation and Configuration of
S3M UPS Models and Battery Cabinets
EOD Battery Volt: End of discharge voltage is the low voltage cutoff of the batteries during a battery mode operation. The
value can be 1.60~1.90. The default value is 1.67V/cell, or 10.02Vdc per battery.
Float Temp Compen Coeff: Modifies the voltage of compensation after enabling the switch. The value can be
0.001~0.007V/cell/°C. The default value is 0.003V/cell/°C.
Boost Charge Setting: Boost charge can be set to Disable or Enable. The default value is Enable.
No Battery Warning: Keep this alarm enabled if you want the UPS to provide a warning when no batteries are present. The
default value is Enable.
64

Publicidad

Tabla de contenido
loading

Tabla de contenido