DEVICE SPECIFIC FEATURES
Internal Indication IIN1-6 (Device trouble): Set to indicate a change in the current DNP
configuration in the outstation. Cleared in the next response. Used to let the master station
know that DNP settings have changed at the outstation. Note that some erroneous
configurations could make impossible to communicate this condition to a master station.
This document also states the DNP3.0 settings currently available in the device. If the user
changes whatever of these settings, it will set the Device Trouble Internal Indication bit on
the next response sent.
Event buffers: device can hold as much as 128 Binary Input Changes, 64 Analog Input Changes
and 64 Counter Input Change. If these limits are reached the device will set the Event Buffers
Overflow Internal Indication bit on the next response sent. It will be cleared when the master
reads the changes, making room for new ones.
Configuration Operation Enable menu: the device can enable or disable permissions for the
operations over al Control Relay Output Block. In case permissions are configured off
(disabled) the response to a command (issued as Control Relay Output Block) will have the
Status code NOT_AUTHORIZED. In case the equipment is blocked the commands allowed
are the configured when permitted. While blocked, the relay will accept commands over the
configured signal. If the equipment is in operation inhibited state, the response to all
commands over the configured signal will have the Status code NOT_AUTHORIZED.
Customers can configure Inputs/Outputs to suit their needs, by means of ZIVercomPlus
software.
Atención
© ZIV Aplicaciones y Tecnología, S.A. Zamudio 2004
Este documento contiene información confidencial propiedad de ZIV S.A. Cualquier forma de reproducción o
divulgación está absolutamente prohibida y puede ser causa de severas medidas legales.
DNP 3.0 : Device Profiles Document
73 of 84
Page