LOCATION AND MOUNTING

The cabinet is designed to be installed indoors, in a safe and secure location. Suggested locations include electrical
rooms, communication equipment rooms, closets or in the ceiling. To save time, wiring and facilitate testing, install
the cabinets at an equal distance between its controlled doors. Normal temperature and humidity levels should be
maintained .
Please note that other approved cabinets with approved tamper switch on the front cover and rear
surface can be used.
Cabinet Dimensions:
29 cm (11.4") high, 28 cm (11") wide, 8 cm (3.15") deep
The Cabinet Can Accommodate:
One 12Vdc @ 4.5AH or 7AH, gel cell type batteries and wiring connections (15cm (6") high, 6cm
(2.5") wide, 9 cm (3.54") deep)
Voltage
12 Volt
12 Volt
Multiple Conduit Knock-outs:
Two 19.05mm (0.75") on each side and one 12.7mm (0.5") on top
Minimum Clearance For Cabinet:
25cm (10") clear space around all sides
38cm (15") clear space in front of cabinet
Minimum Clearance From Electrical Interference:
2.4m (8ft.) from high voltage equipment or wiring and from electrical equipment likely to generate
interference
1.2m (4ft.) from telephone equipment or lines and 8m (25ft.) from transmitting equipment
The system's location and wiring methods shall be in accordance with the National Electrical Code.

MOUNTING INSTRUCTIONS

The box needs to be prepared before fixing it to its location.
38
A22K
High Security Access Control 2-Doors Module
Capacity
Length
7 Ah
151mm (5.94")
4.5 Ah
90mm(3.54")
Width
Height
65mm (2.56")
97.5mm (3.84")
70mm (2.76")
106mm (4.17")
EN