DOOR LOCK DEVICES
Each controller has two lock outputs. The LOCK OUTPUT can be configured to provide power (750mA @ 12Vdc),
see "Jumper Settings" on this page, the LOCK OUTPUT is protected by a fuseless protection algorithm and will
shutdown if the current exceeds 750mA @ 12Vdc. When a different voltage or more current is required, we
recommend to use the RELAY OUTPUT configuration (see "Wiring Diagram of Locking Device", page <OV>).
• If you have one door with a reader on each side of the door, you can use either lock output.
• You can program the lock outputs to function in "fail-safe" (remove power to unlock a door) or
"fail-secure" mode (power required to unlock a door).
• When using electromagnetic door locks or similar devices ensure that the current specifications are
not exceeded.
Always consult the regulatory agency in your area for existing regulations regarding doors designated
as emergency exits.
Jumper Settings
The jumpers LOCK1 and LOCK2 must be set according to the lock devices used (see "Wiring Diagram of Locking
Device", page <OV>).
Jumper Side View
0V
12V
ETHERNET
PORT
+12V DC
RS485
LOCAL
A+
BUS
B-
Input 1
EXTRA
Input 2
INPUTS/
Output 1
OUTPUTS
+12V DC
Output 2
READER DOOR 1
READER DOOR 2
BUZ GRN RED D1
D0 GND 12V
BUZ GRN RED D1
48
A22K
High Security Access Control 2-Doors Module
Lock Output Jumper Settings
There are two jumpers, one for each lock output, LK1 and LK2.
Each output provides 750mA at 12VDC
Default setting:
The lock output will be at 0Vdc in
normal state and toggles to
12Vdc during the unlock time.
(De-energize lock output)
ETHERNET
LOCAL BUS
24V DC INPUT/
STATUS
BATTERY/
MODULE TYPE
SYSTEM STATUS
INPUT
DOOR 1
DOOR 2
D0 GND
12V
C1
GND
REX1
12V
C2
The lock output will be at 12Vdc in
normal state and toggles to 0Vdc during
or
the unlock time. This is the typical
setting for electromagnetic door lock.
LOCK 1 & 2
JUMPER SETTING
INPUT
POWER
SUPPLY
BATTERY
BACKUP
ENCLOSURE
TAMPER
INPUT
LOCK
SWITCH
DOOR 1
INPUT
GND
REX2
12V
GND
TMP
LK1+ LK1-
C1 NO1 NC1
-
+
Jumper Side View
(Energize lock output)
0V
+24V DC
-
+12V DC
-
LOCK
DOOR 2
LK2+ LK2-
C2 NO2 NC2
+
-
EN