Product Information
C79000-Z8974-C064-01
for
DP/EIB Link
'DWHG 
Description of the Product and Functions
DP/EIB Link is a rail-mounted device with standard
dimensions. DP/EIB Link connects instabus EIB with
PROFIBUS DP.
DP/EIB Link is both a PROFIBUS-DP Slave and EIB
device at the same time:
Using DP/EIB Link, you can access any EIB devices
from within PROFIBUS DP; you can
activate switches, and set or modify displays by
writing data records from the DP Master;
query states, detect switching events and
evaluate displays by reading data records.
Using ETS (EIB Tool Software), you can select
application programs, assign specific parameters and
addresses and transfer them to the device.
Application Programs
A diskette containing a GSD file and ETS project file is
supplied with the manual.
Technical Specifications
Power supply
External via 24 V
Response to bus power failure
Turn off (not selectable)
Response to return of bus power supply
Can be selected depending on the application
Controls:
1 teach-in button:
for switch over between normal and addressing
mode
1 BCD coding switch for setting the PROFIBUS
address
Display elements
1 EIB LED:
The LED is lit red after pressing the programming
button once. The DP/EIB Link can now be loaded with
the EIB address (physical address) or the application
using ETS/EIB .

1 POWER LED:

Lit when the 24 V power supply is OK.
1 DP/BF LED
Lit when there are problems on PROFIBUS-DP
1 EIB/BF LED
Lit when there is a problem on the DP/EIB LINK or on
the instabus EIB.
Bus attachments
• PROFIBUS: the PROFIBUS attachment is via the
sub-D female connector
• EIB bus: via standard EIB bus terminals
Mechanical Data
• Casing: plastic
• Dimensions: Rail-mounted device with standard
dimensions,
width 4 MW (1 MW = 18 mm)
• Weight: approx. 220 g
• Fire load: approx. 3050 KJ ± 10 %
Mounting: snap on to rail
DIN EN 50022-35 x 7.5
Electrical Safety
Pollution degree (to IEC 664-1): 2
Degree of protection (to EN 60529): IP 20
Overvoltage category (to IEC 664-1): III
Bus: safety extra-low voltage (SELV) SELV DC
24 V
Device meets
EN 50 090-2-2 and EN 60669-2-1
EMC requirements
Meets EN 50081-2, EN 50082-2 (industrial
environment)
Environmental conditions
Resistance to climate changes: EN 50090-2-2
Ambient temperature in operation: - 5 ...+ 60 °C
Storage temperature: - 40 ... + 70 ° C
Rel. humidity (no condensation): 5 % to 95 %
6GK1415-0AA00
CE Mark
Complying with EMC directive,
Low voltage directive
Position and function of the display and control
elements
See Figure 1
Installation Instructions
The device can be used for fixed installation in
interior rooms, in dry rooms and for installation in
power distribution cabinets.

:$51,1*

• The device must only be installed and put into
operation by a qualified electrician.
• The device must not be connected to 230 V.
• In cable installation tests, that measure core to core
(in contrast to the standard DIN VDE 0100 T. 610),
the device must be disconnected otherwise it can be
destroyed.
• Free rail areas with an inserted data bus should be
covered with cover 5WG1 192-8AA01.
• The relevant safety and accident prevention
regulations must be adhered to.
The device must not be opened. A defective device
must be sent to the appropriate Siemens center.
Installation and Wiring
Bus attachments
Attachment to instabus EIB is via standard EIB bus
terminals on the front panel.
The connection to the 24 V power supply/function
ground is via plug-in terminals.
Installation of the rail-mounted device ( Figure 2)
• Place the rail-mounted device (B1) on to the rail (B2)
and
push in the bottom part of the device until you hear
the catch snap into place.
Removing the rail-mounted device (Figure 2)
• Remove all connected cables (except for
PROFIBUS-DP),
• push down the catch (C3) with a screwdriver and
BCD coding switch
for setting/displaying
PROFIBUS address
Status LEDs
Screwless safety extra-low
plug-in terminals
for connection of external
power supply 24V
• pull out the bottom of the device (C1) from the rail
(C2) and lift it off.
B 2
B 1
)LJXUH  ,QVWDOODWLRQ DQG UHPRYDO RI WKH UDLOPRXQWHG GHYLFH
Further Information and Documentation
A manual and diskette are available for the DP/EIB
Link under the following order number:
6GK1 971-3DA00-0AA0 (German)
6GK1 971-3DA00-0AA1 (English)
If you encounter problems with instabus EIB you can
also contact our training center
at the following number:
+49 941 790 2953
EIB certification
Not yet obtained. Certification is planned at a later
date.
)LJXUH 
Standard EIB bus terminal
for attachment to EIB bus
C 2
C 1
C 3
EIB LED
PROFIBUS attachment
sub-D connector
EIB teach-in button
for EIB
addressing /
programming
Labeling field
(phys. EIB address)