Programmable power transducer SIRAX BT5400
Safety instructions
The unobjectionable and hazard-free operation presupposes that the
safety instructions as well as Device Manual, electronically down-
loadable via www.camillebauer.com, have been read and understood.
The installation and commissioning should only be carried out by trained
personnel.
Check the following points before commissioning:
- that the connection wires are not damaged, and that they are not live during
wiring
- that the power fl ow direction and the phase rotation are correct
- that these product do not have internal fuses
The instrument must be taken out of service if safe operation is no longer pos-
sible (e.g. visible damage). In this case, all the connections must be switched
off. The instrument must be returned to the factory or to an authorized service
dealer.
It is forbidden to open the housing and to make modifi cations to the instrument.
The instrument is not equipped with an integrated circuit breaker. During instal-
lation check that a labeled switch is installed and that it can easily be reached
by the operators.
The device is maintenance free. Unauthorized repair or alteration of the unit
invalidates the warranty.
Application area
The programmable transducer SIRAX BT5400 is to be installed permanently on a
top hat rail and is used to measure apparent, active and reactive power as well as
phase angle and power factor.
Mounting and disassembly
- Any mounting position is possible
- SIRAX BT5400 is mounted on a top hat rail (EN50022)
- Disassembly of the device requires that all connected wires be without current.
First, remove all push terminals and the wires of the current and voltage inputs.
Ensure that possible current transformers are short-circuited before the current
connections on the device are opened.
Electrical connections
A marked and easily accessible current limiting switch has to be
arranged in the vicinity of the device for turning off the power supply.
Fusing should be 10 Amps or less and must be rated for the availab-
le voltage and fault current.
Attention: Danger to life! Ensure that all leads are free of potential
when connecting them!
All voltage measurement inputs must originate at circuit breakers
or fuses rated 1 Amp or less. This does not apply to the neutral
connector. You have to provide a method for manually removing
power from the device, such as a clearly labelled circuit breaker or a
fused disconnect switch.
When using voltage transformers you have to ensure that their
secondary connections never will be short-circuited.
No fuse may be connected upstream of the current measurement
inputs!
When using current transformers their secondary connectors must
be short-circuited during installation and before removing the device.
Never open the secondary circuit under load.
The confi guration of connections is contained in the connection diagram of Figure 3.
Please observe that the data on the type plate (Fig. 1) must be
adhered to !
The national provisions have to be observed in the installation and
material selection of electric lines!
4
Technical data
Measurement inputs
Nominal voltage (U
):
n
Potential transformerprimary value: 100 ... 692,8 kV
Nominal frequency (f
):
n
Rated load input voltage:
Overload capacity:
Rated current (I
):
n
Current transformer primary value:
Nominal frequency (f
):
n
Rated load input voltage:
Overload capacity:
Power supply
Nominal voltage
Frequency range:
Consumption:
Measuring output (1x or 2x)
Output type:
Range:
RS485 output
Protocol:
Baud rate:
Cable length:
Parity:
Cross sections and tightening torques
Terminals 1 ... 8
Single wire: ≤ 4,0mm
2
or multiwire with end splices: 2 x 2,5mm
Torque: 0.5 ... 0.6Nm rsp. 4.42 ... 5.31 lbf in
Terminal A, B, G
2
Single wire: ≤ 1,5mm
or multiwire with end splices: 2 x 0,5mm
Torque: max. 0.5 Nm rsp. 4.42 lbf in
Ambient conditions, general information
Operating temperature:
Temperature infl uence:
Relative air humidity:
Altitude:
Device to be used indoor only!
Safety
Protection class:
Overvoltage category:
Insulation test voltage:
Pollution degree:
Protection:
Parameterization
Complete parameterising of all functions of SIRAX BT5400 is possible via 2
push-buttons on site or via communication interfaces Modbus (RS485). Setting has
to be effected via mechanical DIP switches to enable parameterising of the output
(Fig. 2). The detailed description of the confi guration and parameterization of the
device is described in the device manual.
100 ... 500 V
L-L
L-L
25 ... 60Hz
< 0.6 VA per phase at nominal voltage
1.2 * U
permanently,
n
2 * U
for 1 sec., 10 repetitions in 10 minute
n
intervals.
1 ... 5A
1 ... 9999A
25 ... 60Hz
< 0.2 VA per phase at U
n
1.2 * I
permanently,
n
10 * I
for 3 sec., 5 repetitions in 5 min.
n
50 * I
for 1 sec., in 60 min.
n
60 ... 300V AC/DC ±5%
45 ... 65 Hz
≤ 8 VA for 1 output
≤ 10 VA for 2 outputs
Impressed DC voltage or DC current
(DIP switch & programming).
Bipolar –20 ... 0 ... +20 mA or
–10 ... 0 ... +10 V
A, B, G
Modbus RTU
adjustable 19200, 9600, 4800 or 2400
max. 1200m
Odd or Even with 1 Stopbit,
None with 1 or 2 Stopbits
2
2
0 bis +45 °C
±0,2% / 10 K
< 75% no condensation
≤ 2000 m max.
II
III
50Hz, 1min. (EN61010-1)
3700V, input against all other circuits
3700V, auxiliary power against surface and output
2
IP40 (front), IP20 (housing, terminals)