Descargar Imprimir esta página

XPR Access LCSP-MF Manual Del Usuario página 4

Teclado multiprotocolo con lector mifare integrado

Publicidad

PROGRAMMING FLOWCHART
Change
Select Output Protocol
Master Code
1
1
Enter New
Master Code
Single
Press 6 Digits
Wiegand
Select Type of Wiegand
2
3
1
2
4
Wiegand
Wiegand
Wiegand
Wiegand
34bit
40bit
26bit
30bit
Direct Menu
exit
Entering Menu is always done with B + 000000 if the Master Code is not changed.
Submenu 1 - Change Master Code. The Master Code must be 6 digits. After enrolling new Master Code the LCSP automatically exits the
Menu and the new master code must be typed to enter the menu.
Submenu 2 - Select Type of Wiegand. With this the Keypad can be adjusted to send 4 different Wiegand Outputs. The Wiegand selected
must be the same as the controller's Wiegand Input where the LCSP Keypad is being connected. Example: If you use a controller that
recognizes Wiegand 34bit, then enter the menu of LCSP, press 2, then press 3.
Submenu 3 - Select Output Protocol. The Keypad can send the Code by different Protocols. Use "Single Wiegand" when connected to third
party controllers. When "Single Wiegand" is selected, what is typed on the Keypad the same will be sent as Wiegand Number. Use Double
Wiegand when connected to EWS, use Clock&Data when connected to controller with Clock&Data input, use Codix when connected to Vi200,
EX5, EX7, INOX99 or VKP99.
Submenu 4 - PIN Code Length. If "0" is selected, then any PIN Code with any length can be sent, but the PIN Code is typed with "A" for
confirmation( ex. 123 + A). If 1 to 8 is selected the PIN Code length is determinated by the number selected.
Submenu 5 - Entry Mode. "Only PIN Code" is disabling the proximity and LCSP works as keypad only. "Only Card" is disabling the Keypad
and the LCSP works as Proximity Reader. "Card and PIN Code" defines the double security, both the Card and PIN Code is required for the
Wiegand to be sent. "Card or PIN Code" enables normal operation.
Submenu 6 - Presets.
The Presets are set of preprogrammed parameters for easy programming.
6-1 "Wiegand 26bit Normal" -
6-2 "Wiegand 34bit Normal" -
6-3 "Wiegand 34bit EWS Mode" -
6-4 "Wiegand 26bit EWS Mode" -
6-5 "Codix" -
Presets 6-3 and 6-4 to be used always when LCSP is connected to EWS firmware ver.2.42 or higher.
Submenu 7 - Site Code Length. S
Submenu 8 - Enter Site Code. Put the site code always in 5 digit format (ex. 00170).
Submenu 9 - Backlight. Turns ON/OFF the backlight.
Enter "Master Code"
1 small beep + 1 long beep + Orange LED is 'ON'
3
2
3
4
1
Double
Clock &
Codix
only PIN
Data
Code
Wiegand
PIN Code Length
4
0
1 - 8
for any length
for lengths
with "A"
between
in the end
1 to 8 digits
Press "A" to validate
Type: Wiegand 26bit; Output: Single Wiegand; PIN Length: 4 digits; Entry Mode: Card or PIN Code
Type: Wiegand 34bit; Output: Single Wiegand; PIN Length: 4 digits; Entry Mode: Card or PIN Code
Type: Wiegand 34bit; Output: Double Wiegand; PIN Length: 4 digits; Entry Mode: Card or PIN Code
Type: Wiegand 26bit; Output: Double Wiegand; PIN Length: 4 digits; Entry Mode: Card or PIN Code
Output: Codix; PIN Length: any length with "A" in the end; Entry Mode: Card or PIN Code
et the code length sent to Host
B + 000000
No
Validation OK?
Yes
Entry Mode
5
2
3
4
Card and
Card or
only
PIN
PIN
Card
Code
Code
Presets
6
3
1
2
Wiegand
Wiegand
Wiegand
34bit
34bit
26bit
normal
normal
EWS
and exit the menu
(orange LED OFF)
. Defaul is "0". To be used only in specific cases.
Error Beep
(3 short beeps)
Site Code Length
7
3
1
2
4
Site Code
Site Code
Site Code
No Site
between
between
between
Code
0 to 15
0 to 255
0 to 65535
4
5
Wiegand
Codix
26bit
EWS
Backlight
9
0
1
Backlight
Backlight
OFF
ON
Enter Site
Code
8
5 digits
4

Publicidad

loading