• Repair possible obstruction of the centrifugal blower or condenser fan; If the error persists,
replace the centrifugal blower or condenser fan (to access the blower or fan, remove the
outer cover of the device and the evaporator cover for the centrifugal blower).
• Replace fuse 7.5A. To access the fuses of the centrifugal blower or condenser fan, remove
the access cover of the electronic control located on the internal air distribution panel.
• Replace electronic control.
!
(If the error persists contact an Authorised Service Centre).
• Connect terminals of the compressor's electronic module correctly. (According to electrical
diagram attached).
• Replace electronic module/s on the compressor/s.
• Replace compressor/s.
• Check pressure (from 6 bars the compressors switch off), if necessary recover gas and
reload 250 grams per circuit.
!
To access compressors, modules or charging jacks you must remove the device's
outer cover.
!
(If the error persists contact an Authorised Service Centre).
• Reprogram control.
• Replace control's battery and reprogram.
• Replace electronic control (to access, remove the access cover on the electronic control
located on the inner air distribution panel).
• Replace control.
!
(If the error persists contact an Authorised Service Centre).