Installation Instructions - e-conolight E-AL Serie Instrucciones De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTALLATION INSTRUCTIONS

E-AL and E-APA Series
FIGURE 2
5/16" (8 mm) bolts
Adjustment Screw
Yoke Mount with 5/16"
(8 mm) bolts to strong
solid surface .
2" (51 mm)
Figure 3 — 2" (51 mm) Adjustable Fitter Positions
30˚
30˚
30˚
30˚
30˚
15˚
30˚
Figure 4 — Yoke Mounting (U-Bracket)
Align these Two Trunion Holes
Adjustment Screw and Holes
Lock
Washers
Hex Nuts
Cord
Lock Washer
between Trunions
Outer Trunion
Inner Trunion
(Assembles to the Housing)
2" (51 MM) ADJUSTABLE FITTER MOUNTING
NOTE: Fixture is only UL listed for downlight orientation.
1. Install gasket on upper fitter by aligning the (2) holes in the gasket
with the (2) threaded bolt holes in the upper fitter.
2. Open fixture by removing ribbed driver compartment cover.
3. Align (2) threaded bolt holes on the upper fitter with the (2) bolt
holes in the side of the fixture.
4. Fasten upper fitter to the fixture using the (2) bolts and lock
washers supplied with fitter. Tighten bolts to 132 in-lbs (15 Nm).
2" (51 mm) Adjustable Fitter
over 2" (51 mm) pipe.
Typical Pole Mounted Positions
Major Divisions: 15˚
90˚
Cord Grip
Sealing Washers
Hex Bolts
Housing
(Cross Section View)
www.e-conolight.com
|
Document:
LPN00365X0001A0_A
Created By:
TMT
5. Remove splice compartment cover from upper fitter.
6. Route fixture ground wire, common wire, and voltage wire thru
fixture and into the fitter.
7. Replace ribbed driver compartment cover that was removed in Step
2 above.
8. Strain relief is required for electrical connections on 2" (51 mm)
adjustable fitter mounts at heights of 25' (7.6 m) and above. Tie
a knot in the supply wires above the hole in the upper fitter wiring
compartment to reduce the strain on the connections. Make sure
knot will not slip through hole.
9. Slip lower fitter over 2-3/8" (60 mm) o.d. heavy wall pipe or tenon
and securely tighten two Allen head set screws with 3/16" Allen
wrench to 140 in. lbs. (16 N•m). See Figure 2.
10. Complete electrical connection in splice compartment.See Fixture
Wiring section.
11. If photocell accessory is used, locate in cover of fitter splice
compartment. See photocell installation sheet for details.
12. Tighten 3/8" bolt in fitter splice compartment to 19 ft. lbs. (25 N•m).
13. Replace splice compartment cover.
YOKE MOUNTING (U-BRACKET)
E-ACU FOR USE WITH E-APA12 SERIES
E-ACUH FOR USE WITH E-APA23 SERIES
NOTE: Fixture is only UL listed for downlight orientation.
1. Open fixture by removing ribbed driver compartment cover.
2. Insert the hex bolts with sealing washers through the housing and the
U-bracket.
IMPORTANT: When installing sealing washers make sure the rubber
side is facing the inside of the fixture housing wall.
3. Secure U-bracket to housing with (2) 5/16" hex nuts and lock
washers (as shown in Figure 4). Tighten to 132 in. lbs (15 Nm).
4. Insert cord thru cord grip so that the leads with the ground lug extend
from the threaded side of the cord grip by 4" or as needed to reach
ground lug in fixture. Tighten cord grip firmly to cord.
5. Insert cord into fixture and fasten cord grip to housing as shown in
Figure 4.
6. Connect cord ground wire to fixture ground. Connect cord white wire
to driver common wire. Connect cord black wire to driver voltage
wire.
7. Reattach ribbed driver cover removed in Step 1.
8. Mount fixture using two 3/8" (10 mm) bolts appropriate for mounting
surface. See Figure 5.
9. Complete wiring to power source as indicated under Fixture Wiring
section.
10. Use the locking screw provided to secure the U-bracket in a fixed
position, being sure to line up a set of locking holes in both brackets.
Securely tighten both bolts on sides of U-bracket.
Figure 5 –– Mounting to Surface
888.243.9445
|
FAX: 262.504.5409
Date:
2017-02-20
007091

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

E-apa serie

Tabla de contenido