Installing the power cables
Connection diagram
Supply disconnecting
device (disconnecting
means) with fuses
CHK-xx mains choke
(optional)
JFI-xx mains filter
(optional)
ACS850-04
UDC+ UDC–
U2 V2 W2
V1
U1
3 ~
Motor
Notes:
- If shielded supply (input) cable is used, and
the conductivity of the shield is not sufficient
(see the table below), use a cable with a
ground conductor (1) or a separate PE cable
(2).
- For motor cabling, use a separate ground
cable (3) if the conductivity of the cable shield
is not sufficient (see the table below) and the
cable has no symmetrical ground conductors.
Cross-sectional area of
one phase conductor
(S)
2
S < 16 mm
2
2
16 mm
< S < 35 mm
2
35 mm
< S
L1 L2 L3
(PE)
1)
U1 V1 W1
R
R+
–
3)
W1
Braking resistor
PE
(optional)
Minimum cross-
sectional area of
protective conductor
(S
)
p
S
2
16 mm
S/2
(PE)
2)
PE
Quick installation guide - ACS850-04