Cabling
Neutral bus and auxiliary contacts
Cabling / Neutral bus (optional)
1
Use 5/32 hex key/wrench. See chapter Installation / Neutral
assembly (optional).
Non-fusible safety switch catalog number
AMPS
Suitable neutral bus, catalog number
Neutral bus / terminal lugs
Terminal lug
Torque: wire tightening
Torque: wire tightening
Lug mounting torque
Wire range
Cabling / Auxiliary contacts (optional)
Use Pozi-drive #2 or flat blade screwdriver. See chapter
Installation / Auxiliary contacts (optional).
Auxiliary contacts, catalog numbers OA1G10 (1NO), OA3G01 (1NC)
NEMA
Wire size
Torque
1/8 Ratings | Instruction Bulletin EOHU361K, EOHU362K, EOHU363K, 1SCC340035M1402 / B
A
Copper
lbs.in
Nm
Aluminum
lbs.in
Nm
lbs.in
Nm
AWG
mm
2
A600, R300
1 - 2 × #18 - 14 AWG
1 - 2 × 0.75 - 2.5 mm
2
7 lbs.in
0.78 Nm
EOHU361K
EOHU362K
30
60
EOHXSN13
EOHXSN13
OZXA-100
OZXA-100
35
45
3.9
5.1
40
45
4.5
5.1
132
132
14.7
14.7
#14 - 2/0
#14 - 2/0
2.5 - 70
2.5 - 70
EOHU363K
100
EOHXSN13
OZXA-100
50
5.6
50
5.6
132
14.7
#14 - 2/0
2.5 - 70