ABB EOHU Serie Boletín De Instrucciones página 16

Ocultar thumbs Ver también para EOHU Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation
Wiring
1
L
1
3
G
Wiring
Connect the power wires to the switch terminals and connect
the ground wire to the ground terminal block inside the
enclosure. Refer to the National Electric Code and all local
codes for appropriate wire size and grounding requirements.
See chapter Cabling.
All cables must have 167 °F / 75 °C minimum rating.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
See general safety instructions on page 1/2 before proceeding.
Failure to follow these instructions will result in death or serious injury.
1/12 Installation | Instruction Bulletin EOHU361K, EOHU362K, EOHU363K, 1SCC340035M1402 / B
Safety
switch
Line side and load side
size [A]
terminal lugs
Wire range AWG / mm
2
30
#14 -8 / 2.5 - 6
60
#14 -3 / 2.5 - 25
100
#14 -1 / 2.5 - 35
Wire strip length L
ALL
0.55 - 0.63 in
14 - 16 mm
Wire tightening torque for
Cu and Al cables (wire size)
[lbs.in (#)]
[Nm (mm
30
35 (#14 - 10)
3.9 (2.5 - 4)
40 (#8)
4.5 (6)
60
45 (#6 - 4)
5.1 (10 - 16)
50 (#3)
5.6 (25)
100
50 (#3 - 1)
5.6 (25 - 35)
Ground bus
#14 -2 / 2.5 - 35
#14 -2 / 2.5 - 35
#14 -2 / 2.5 - 35
0.39 - 0.47 in
10 - 11.9 mm
Wire size / tightening torque
)]
[# / lbs.in]
[mm
/ Nm]
2
2
8 / 40
6 / 4.5
6 / 45
10 / 5.1
8 / 40
6 / 4.5
6 / 45
10 / 5.1
4 / 45
16 / 5.1
2

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Eohu361kEohu362kEohu363k

Tabla de contenido