Pin Assignment
Tandem Safety Function
For the operation of 2-3 drives on separate vents the
tandem safety function (TMS) may not be used! For
this the TMS line (yellow) of the connection cable
CDC-PC xxxx of the drives is disconnected, so that
the remaining drive(s) are still opened in case of fire
in the event of a failure, under voltage or overload
cut-out.
*
CDC-PC xxxx-T01
99.823.30 2.4/03/16
Standard
YE (TMS)
OG (n.c.)
GN (n.c.)
BN (Mot. b)
WH (Mot. a)
*
* TMS line must
be disconnected!
Option -BRV
YE (TMS)
OG (n.c.)
GY (BRV)
GN (n.c.)
BN (Mot. b)
WH (Mot. a)
PK (n.c.)
Mot. a
Mot. b
(WH)
(BN)
Whenever two drives are operated on a single sash,
the tandem safety function can be used. This
function connects the cut-offs of the two drives in
such a way that if one drive is cut off due to overload,
the other drive will also be cut off.
In this case active jamming protection may not
activated!
CDC-PC xxxx-T01
English
Option -SGI
YE (TMS)
OG (n.c.)
GY (-SGI)
GN (+SGI)
BN (Mot. b)
WH (Mot. a)
PK (n.c.)
(WH) white
(BN)
brown
(OG) orange
(YE)
yellow
(GN) green
(PK)
pink
(GY)
grey
CDC 200/350
7/16