Once the system is wired (per Figure 8), the power conductors wired to the DIN rail terminals
inside the Pentair Pentek Solar Drive should be tightened with torque values of:
– Solar PV and motor load conductors: 11 lb-in
– AC source conductors: 8 lb-in
The cable glands (cord grips) on the bottom of the enclosure should be used as follows:
– 1/2 inch cord grips should only be used with a cord that is 0.280-0.455 inch outer diameter.
– 3/4 inch cord grips should only be used with a cord that is 0.455-0.705 inch outer diameter.
When all conductors are wired into the controller, the cover (enclosure door) should be replaced
and tightened using the cover screws to 2-3 in-lb or equivalent.
Terminal 1
(Yellow)
Terminal Aux
(Gray)
Yellow
Red
Black
Float Switch/
Other Sensors
Single phase motor loads should be wired as shown in Figure 8. Single phase 3-wire motors
should be wired so that the Common Lead is wired to Phase A, Starting Winding to AUX and Main
Winding to Phase C. Use DIP Switch 8 for proper single phase motor selection.
IMPORTANT:
Three Phase Motor
Terminal 1 (Yellow): YELLOW wire
Terminal 2 (Red): RED wire
Terminal 3 (Black): BLACK wire
10
SOLAR DRIVE WIRING INSTRUCTIONS
*
Single
Phase
3-Wire
Motor
Figure 8: Wiring Inside the Pentair Pentek Solar Drive
Solar PV 2
Three
Solar PV 1
Phase
Motor
Single Phase 3-wire Motor
Terminal 1 (Yellow): YELLOW wire – common motor lead
Terminal Aux (Grey): RED Aux wire – start motor lead
Terminal 3 (Black): BLACK wire – main motor lead
Terminal 2
(Red)
Terminal 3
System
Ground
P1062 (06/06/19)
(Black)
Red
Black
Red
Black