In order to take the best advantage of the features that this power supply has to offer and
to ensure long term reliability for your equipment, please read these instructions carefully
before installation and use. They should be retained for future reference.
1
2
OUT
DC24V/2.5A
Uout ADJ.
3
22,5-28Vdc
L
IN
4
110-240VAC
N
Art.No. 50132582
38
38
76
38
AC230V
L
N
Art. Nr. 50132582
L
N
Art. Nr. 50132582
9
AC230V
L
N
Art. Nr. 50132582
L
N
10
Art. Nr. 50132582
(1) General
This unit employs many features previously unavailable in an industrial power supply. It
has been designed to withstand the high levels of interference found in heavy industry and
has emission levels low enough for it to be used in residential, commercial and light
industrial environments.
The PSU-02A-1P-24V-S has a high level of reserve power. This enables loads with
significant inrush current to be supported and will also ensure that circuit breakers will trip
in event of short circuit.
A protective feature is provided which will take control as the unit approaches the power
limit due the overload or excessive temperature brought about by lack of ventilation.
This equipment shall be connected directly to the d.c. supply system earthing electrode
conductor or to a bonding jumper from an earthing terminal bar or bus to which the d.c.
supply system earthing electrode is connected.
Operating instructions
Power Supply Unit 1 PHASE
PSU-02A-1P-24V-S
5
TA
6
7
28 VDC
30
24 VDC
25
20
15
2
10
5
0,5
1,5
1,0
2,0
2,5
Uin 95 - 265 VAC /
Uout 24 VDC - 2,5 A
3.0
2.5
2.0
1.5
1.0
0.5
0.3
IND.CONT.EQ
1VD7
(2) Technical specification, Art. No. 50132582
Nominal voltage
Input voltage range
Input current, I
om.
Inrush current
Efficiency, typ.
Power factor, typ.
Internal fuse F1:
External fuse max. 10 A
Safety class
Output voltage, adjustable 22,5 - 28 VDC
Static regulation accuracy
Dynamic regulation accuracy typ.
Start-up time
Hold up time of the output, typ.
Output current, continuous
95 - 195 VAC
Voltage
195 - 265 VAC
Voltage
Output current, short circuit , max. 200 ms
Output ripple
Overloading / temperature protection
Relative humidity
Operation temperature
Storage temperature
Protection class, case, EN 60529
Dimensions W x H x D x TA; Weight
(3) Features
[1] Output terminal:
Conductor sizes
Solid
Stranded
Stranded with ferrule without / with plastic sleeve
8
Ferrule minimum lenght must be
Tightening torque:
[2] Output voltage "OK", indicator light
[3] Output voltage adjust 22,5 - 28 VDC
[4] Input terminal:
Conductor sizes
Solid
Stranded
Stranded with ferrule without / with plastic sleeve
Ferrule minimum lenght must be
Tightening torque:
(4) Location
3,0
3,5
The power supply is cooled by natural convection. It is important to maintain clearance
to other components as much as possible to ensure best performance and long term
stability. Top and bottom clearances should be 50 mm at minimum. Side clearance to
other equipment should be 20 mm or > 50 mm if that equipment is heat generating. The
ambient temperature should be measured on the underside of the unit. There will be
an increase of 25°C at the top. If natural convection is restricted, forced cooling should
11
be used. Mounting should comply with EN 60950-1 point 4.7 and 4.6.1. Protection class
of the case IP20 (EN 60529).
(5) Mounting [7]
The rail should be fixed solidly so that it cannot twist when mounting or removing the
unit. Mounting instructions [5], Removing instructions [6].
(6) Switching on
Factory set, ready to use, check the connection diagrams for parallel and series
connection.
(7) Loading capacity
The nominal current is 2,5 A (60W) but due to the nature of industrial loading, the power
supply has been designed to support loads with high inrush currents without damage or
shutdown. Curve [8] shows the typical current / voltage curve, decreasing part of the
curve shows the current limitation. Curve [11] show the current / temperature limit.
(8) Parallel connection [9]
Up to 5 units may be connected in parallel. The open circuit voltage of each unit should be
set to same value. Accuracy of setting will determine how well the units share the load
current. The gauge and lenght of the cable between each power supply and the common
point should be the same. Units should only be used in parallel where the supply exceed
110 VAC.
(9) Series connection
Up to 2 units may be connected in series to give either 48 VDC or +/-24 VDC. Check
the connection diagram [10].
(10) Using circuit breakers on the power supply output:
On the short circuit, the power supply will trip, for example, the following ABB-STOTZ
circuit breaker:
(11) Standards
Electrical safety
EMC
Immunity
Emissions
We reserve the right to change this specification.
110 - 240 VAC 50/60 Hz
95 - 265 VAC 50/60Hz, 110 - 300 VDC
1,2 A
/ 110VAC - 0,63 A
rms
< 20 A / 230 VAC after 1 ms
85% / 110 VAC - 87% / 230 VAC
0,59 / 110 VAC - 0,48 / 230 VAC
T 2,5 A 250 V Littelfuse
(UL listed Bussmann Typ. AGC-10A or
Littelfuse No. 314 010) or ABB S201-B10A
0->100%, 5% 1ms / 100%->5%, 5% 1ms
> 15 ms / 110 VAC - > 80 ms / 230 VAC
24 VDC - 2,5 A (+40°C) / 1,5 A (+70°C)
28 VDC - 2,0 A (+40°C) / 1,0 A (+70°C)
24 VDC - 2,5 A (+55°C) / 2,0 A (+70°C)
28 VDC - 2,0 A (+55°C) / 1,5 A (+70°C)
derating between 40°C - 70°C, -0.03 A / °C
5 - 95% , no condensing
Voltage 95 - 195 VAC / -25°C - +40°C
Voltage 195 - 265 VAC / -25°C - +55°C
38 x 76 x 100,5 x 7,5 mm; 0,23 kg
0,4 - 0,5 Nm / 3,5 - 4,4 lb. in.
0,4 - 0,5 Nm / 3,5 - 4,4 lb. in.
- S201-Z1,0A
EN 60950-1, UL 60950-1:2003, UL 508, SELV
EN 61204-3 (2000), (EMI:class B, EMS:industry class)
EN 61000-4-2 (1995) ESD 4/8 kV
EN 61000-4-3 (1996) Rf-field 10 V/m
EN 61000-4-4 (1995) EFT/B 2/2 kV
EN 61000-4-5 (1995), Surge 1/2 kV; 500 V
EN 61000-4-6 (1996) Cond. Rf 10 V
EN 61000-4-11
ENV 50204 (1995) Rf-field 10 V/m
EN 60204-1, 60 V / 1 s
EN 55022 B, RF-emissions
EN 61000-3-2, class A
V1.0
/ 230VAC
rms
1
24 VDC
+/- 1%
< 0,3 s
> 10 A / 230 VAC
< 50 mV
rms
Yes
-25°C - +85°C
IP20
1,5 - 2,5 mm² / 16 - 14 AWG
1,5 - 2,5 mm² / 16 - 14 AWG
1,5 mm² / 16 AWG
≥
10 mm
0,75 - 2,5 mm² / 18 - 14 AWG
0,75 - 2,5 mm² / 18 - 14 AWG
0,75 mm² / 18 AWG
≥
10 mm