5. Fonctionnement
5.1 Hiérarchie de l'écran LCD
Level 3
Level 3
Power ON/OFF
Level 1
System Status
Level 2
Main Menu
Level 3
Status
Level 4
System
Supply Air T/ Supply Air RH/
Return Air T/ Return Air RH/
Remote Ch1-4/ Air Volume/
Water In T/Water Out T/
Water Flow/ Valve FB/ Valve Com/
Fan Com/ Heater Com/ Humidifier/
Fan 1-8 Abnormal/ Fire Active/
Smoke Active/ Filter Failed/
Drain Pan Full/ Leak Active/
Wire Leak Open
Run Hours
System/ Filter/ Fan 1-8/
Ball Valve
Event Log
(Figure 5-1 : Hiérarchie de l'écran LCD)
Level 1
Alarm List
Level 3
*The user's
Setting
Administrator
password
required.
Level 4
Setpoint
Supply Air T
Local Setting
ID/ Contrast/ Buzzer/ Language/
User PW Unit/ Delay On/ Baud Rate/
Total Alarm
Controller
Force Mode/ P Gain/ I Gain/
D Gain/ Min Flow T/ Max Flow T/ Fan Step/
Group Work/ Auto Recover/ Intelligent/
Leak. Cut-Off
Set Alarm
Level 5
Sensor Alarm
Return Sensor/ Supply Sensor/
Remote Sensor 1/ Remote Sensor 2/
Remote Sensor 3/ Remote Sensor 4/
Water In Sensor/ Water Out Sensor/
Flow Meter/ Leak SEN.
Actuator Alarm
Ball Valve Error/ Fan 1-8 Failed
Out Of Range
Return T High/ Return T Low/
Return RH High/ Return RH Low/
Supply T High/ Supply T Low/
Supply RH High/ Supply RH Low/
Remote 1 T High/ Remote 1 T Low/
Remote 1 RH High/ Remote 1 RH Low/
Remote 2 T High/ Remote 2 T Low/
Remote 3 T High/ Remote 3 T Low/
Remote 4 T High/ Remote 4 T Low/
Water In T High/ Water In T Low/
Water Out T High/ Water Out T Low/
Water Flow High/ Water Flow Low
144
*The admin password
required.
Level 4
Manual Mode
Fan Speed/ Ball Valve/ Humidifier/ Shutdown Humi/
Humidifying stop/ Backlight/ Buzzer/ Total Alarm/
Chiller Pump/ Heater 1-3/ Main LED/ Standby LED/
Warning LED/ Fault LED
FW Version
System
Level 5
Installation
Type
Set Admin PW
Clear Log
Factory Setting
Reset Component
Filter/ Fan 1-8/ Ball Valve
Set Run Hours Time
Intelligent
ATS Disable
System EPO Action
(Leak/ Fire/ Smoke)
Valve Dir.
Group Timeout