Maintenance

Basic Maintenance

Warning: The UPS system is very heavy. Use appropriate caution
and assistance when moving or lifting it. Do not place anything on
the roof of the rack enclosure.
Recommended Tools: Canned Air
1
Keep the area around the UPS system clean and dry.
2
Operate the UPS system at indoor temperatures between 32° F
and 104° F (between 0° C and 40° C) only. For best results, keep
indoor temperatures between 62° F and 84° F (17° C and 29° C).
3
Leave at least six inches of open space at the front and rear of the
UPS system for proper ventilation.
4
Periodically use canned air or a lint-free cloth to remove dust
build-up from the UPS system cabinets. Use canned air rated for
use with electronic components only.
External Battery Pack Replacement
Warning: The UPS system is very heavy. Use appropriate caution
and assistance when moving or lifting it. Do not disconnect the
battery pack when the UPS system is operating from battery. (The
control panel's LCD screen displays "ON BATTERY MODE"
and the "BATTERY" LED illuminates when the UPS system is
operating from battery.)
Recommended Tools: Phillips Screwdriver
1
Press the "OFF" button
system beeps, then release the button. Press the OFF button again
to enter Bypass Mode. The control panel's LCD screen
should now display "BYPASS MODE".
2
Disconnect the male battery cable connector from the female
I
battery connector
at the rear of the UPS power module.
3
Remove the screws from the battery pack's mounting ears.
4
Using an assistant, remove the battery pack from the rack.
5
Using an assistant, mount the new battery pack in the rack. (Refer
to Mounting section if necessary.)
6
Connect the new battery cable to the female battery connector
at the rear of the UPS power module.
7
Press the control panel's "ON" button
beeps, then release the button.
8
D
The LCD screen
"ECONOMY MODE", depending on the option selected
previously.
201102089 93-2982.indb 15
H
on the control panel until the UPS
G
until the UPS system
should display "ONLINE MODE" or
6 inches
(front)
Open Space for Ventilation
D
UPS System Rear Panel
I
15
15
6 inches
(rear)
RACK (SIDE)
I
D
F
G
E
Control Panel
7/11/2011 3:49:17 PM
H