ONDULADOR CC/CA 1300VA para aplicación Industrial y Ferroviaria
1300VA DC/AC INVERTER for Industrial and Railway application
DIMENSIONES
www.premium.es
/ DIMENSIONS
SIZE-1
SIZE-2
INSTALLATION
• The unit has 4 threaded holes for the fixation on a mounting
surface.
• The unit has internal fans. For an appropriate cooling, the air
input and output should be free of elements that cause and an
air flow reduction (minimum recommended distance to other
objects 50mm).
• Make connections as shown in the figure.
For safety reasons, the following requirements must be met:
• Provide the equipment with some kind of protective enclosure
that complies with the electrical safety directives in effect within
the country where the equipment is installed.
• Include an input fuse with a rating immediately higher than the
maximum input current.
• Use cables of adequate cross-section to connect inputs and
outputs. The following table lists the maximum currents and the
minimum cross-sections for the cables used for each power
connection.
Current
Cable cross
section
3/7
ODX-1300
Input
Input
Input
Output
24V
72V
110V
250V
70 A
24.4A
16 A
3.1A
16
2.5
1.5
0.75
2
2
2
2
mm
mm
mm
mm
04-01-2018
9502145-3
Output
400V
1.88 A
0.75
2
mm
CA-563-3