Installation
2-2
Input Power Cord Connection (Select
Models with Unattached Power Cords
Only): Insert the IEC 60320 C19
(PDUMH20HVNET) or IEC 60320 C13
(PDUMH15HVNET) connector
input power cord into the IEC 60320
C20 (PDUMH20HVNET) or IEC 60320
C14 (PDUMH15HVNET) inlet
PDU. Connect the other end of the input
power cord
AC power, such as a UPS system, PDU
or utility outlet. The PDU should be
provided with over-current protection:
PDUMH20HVNET should be provided
with a maximum 20A branch-rated over-
current protection device;
PDUMH15HVNET should be provided
with a maximum 15A branch-rated over-
current protection device.
Note: The AC power source should not share
a circuit with a heavy electrical load (such as
an air conditioner or refrigerator).
2-3
Connect Input Power Cord
(PDUMH15NET and PDUMH20NET):
Connect the input plug
compatible source of AC power, such as
a UPS system, PDU or utility outlet. The
PDU should be provided with over-
current protection: PDUMH15NET with a
maximum 15A branch-rated protection
device. PDUMH20NET with a maximum
20A branch-rated protection device.
2-4
Equipment Power Cord Connection:
Insert the IEC 60320 C14 connectors
of the equipment power cords into the
IEC 60320 C13 output receptacles
the PDU (PDUMH15HVNET and
PDUMH20HVNET). Insert power cords
into the NEMA 5-15R output
receptacles
5-15/20R output receptacles
(PDUMH20NET). The LED
output receptacle illuminates when the
receptacle is ready to distribute live AC
power. The digital load meter
display the total connected equipment
load in amps.
Networking the PDU
For network configuration instructions, please refer to the WEBCARDLX owner's manual (PN
93358E) included with this product.
21-03-425-93368A.indb 5
21-03-425-93368A.indb 5
of the
A
of the
B
to a compatible source of
C
to a
A
(PDUMH15NET) or NEMA
B
B
near each
C
will
D
PDUMH15HVNET
2-2
PDUMH20HVNET
A
2-3
PDUMH15NET/PDUMH20NET
PDUMH15HVNET/PDUMH20HVNET
A
of
B
2-4
5
88
B
A
B
88
A
C
B
15
D
A
C
PDUMH15NET
B
D
C
PDUMH20NET
B
D
C
4/5/2021 2:41:45 PM
4/5/2021 2:41:45 PM
C