Features
• assembled in USa
• Fits most lever/tee type ball valves up to 2"
• Fits most backflow preventers up to 2"
• Operates on open or closed valves
• Includes mounting hardware to supervise coils on most
solenoids
• accommodates up to 12 aWg wire
• Optional field installed cover tamper switch kit (0090224)
• RoHS compliant
NOTICE
Before any work is done on the fire sprinkler or fire alarm system, the
building owner or their authorized representative shall be notified.
Before opening any closed valve, ensure that opening the valve
will not cause any damage from water flow due to open or missing
sprinklers, piping, etc.
Important: This document contains important information on the installation and operation of the RBVS Universal Ball Valve/Solenoid Coil Supervisory
Switches. please read all instructions carefully before beginning installation. a copy of this document is required by NFpa 72 to be maintained on site.
Description
The Model RBVS is designed to monitor the fully open or closed
position of a ball valve installed in a sprinkler system as well as monitor
the position of a coil on a solenoid for a preaction/deluge system. The
unit will fit on most ball valves installed on back-flow-preventers and
alarm trim lines of dry, alarm, and deluge sprinkler valves. The switch
operates if the ball valve handle is moved from the normal position.
However, the switch does not track the position of the handle or ball.
When the ball valve handle is under the RBVS plunger, a spring-loaded
actuator will contact the valve handle. When the handle is moved from
the position, this actuator extends to the tripped position, and the RBVS
contacts change state, thereby opening or closing a circuit.
The unit also includes a small "L" bracket and "V" clamp to allow the
RBVS to mount directly to the nipple on the coil of a solenoid valve.
The plunger of the RBVS is actuated by the stud protruding through the
center of the coil, see Fig. 6. If a technician removes the coil from the
solenoid for testing, the RBVS will activate.
a cover tamper switch is available and is activated by the removal of the
RBVS housing cover. If an attempt is made to remove the RBVS by the
removal of the mounting brackets, the unit will be set into the tripped
mode by this action.
The RBVS can be mounted to the hex portion of the ball valve or back-
flow-preventer or to the adjoining pipe via two clamps. The RBVS is
shipped with three sets of mounting kits to accommodate various pipe
and valve sizes, refer to Table 1. an "L" shaped and offset bracket for
mounting the switch enclosure and an extension bracket add to the
mounting flexibility of the RBVS. See "Typical Mounting Diagrams"
and "Installations and Operation" on following pages.
Potter Electric Signal Company, LLC
Technical Specifications
Dimensions
Shipping
Weight
enclosure
Temperature
Range
Optional
Housing Cover
Tamper
Contact Ratings
environmental
Limitations
Conduit
entrance
*Specifications subject to change without notice.
St. Louis, MO
5401603 - REV A
Universal Ball Valve/Solenoid
Coil Supervisory Switch
With Large Clamps: 6" L x 5" W x 5.3" H (15,2 cm L
x 12,7 cm W x 13,2 cm H)
With Small Clamps: 6" L x 4" W x 5.3" H (15,2 cm L
x 10,2 cm W x 13,2 cm H)
With Solenoid Clamp assembly: 5.1" L x 3.3" W x 6"
H ( 13 cm L x 8,38 cm W x 15,24 cm H)
1.65 lbs.
Non-Corrosive Composite Material
-40°F to 150°F (-40°C to 65°C)
Cover incorporates tamper resistant fasteners
that requires a special key for removal. One key
is supplied with each device. For optional cover
tamper switch kit, order Stock No. 0090224. See
bulletin #5401598
SPDT Contact: (Form C) 10.1A at 125 VAC
SPDT Cover Tamper: 5A at 125 VAC
NeMa 4 (Ip66)
Not for use in hazardous locations
Use suitably rated conduit and connections
One Knockout for 1/2" conduit connection provided
(See Notice on page 6)
Phone: 800-325-3936
1/20
RBVS
2A at 30 VDC Resistive
10 mAmps minimum at 24 VDC
1mA at 5 VDC min
www.pottersignal.com
page 1 OF 12

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Potter RBVS

  • Página 1 Important: This document contains important information on the installation and operation of the RBVS Universal Ball Valve/Solenoid Coil Supervisory Switches. please read all instructions carefully before beginning installation. a copy of this document is required by NFpa 72 to be maintained on site.
  • Página 2 Conduit Red Solenoid 1, 2(x2), 10 13, 21 11(x2), 12(x2), 16, 17(x4), 18, 19, 20(x2) Valve “Nipple” Mounting Kit (Fig 6) Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com • 5401603 - REV A...
  • Página 3 BRACKET EXTENSION 4.5” permits the actuator to contact the valve handle. Cut and remove HEX BOLT (18) the plastic coating from the ball valve handle to allow the RBVS WASHER (19) SCREW-TAMPER TAMPER actuator to contact and be activated by the metal of the handle.
  • Página 4 Cut and remove 1/2"-2" BALL VALVE the plastic coating from the ball valve handle to allow the RBVS GRIPPERS (2,6) actuator to contact and be activated by the metal of the handle.
  • Página 5 Attach the (bracket-mounting solenoid) from the Red bag to the RBVS through the two smaller slots in the bracket with two tamper resistant screws. 10. Slide the bracket up against the stop on the back of the RBVS and tighten the tamper resistant screws. INSERT NUTS #10-32 INTO BOTTOM CLAMP (11) 11.
  • Página 6: Ordering Information

    Coil Supervisory Switch Tamper Switch Connections Testing The RBVS and its associated protective monitoring system should be tested in accordance with applicable NFpa codes and standards and/or the authority COVER TAMPER & RBVS CONNECTED TO THE SAME ZONE ON THE FACP having jurisdiction (manufacturer recommends quarterly or more frequently).
  • Página 7: Características

    Nota importante: este documento contiene información importante sobre la instalación y el funcionamiento de los interruptores universales de supervisión para válvulas de bola o bobinas de válvula solenoide RBVS. Lea detenidamente todas las instrucciones antes de comenzar la instalación. Según la norma NFPA 72, es necesario guardar un ejemplar de este documento en sitio.
  • Página 8: Kits De Montaje

    1, 2(x2), 10 13, 21 11(x2), 12(x2), 16, 17(x4), 18, 19, 20(x2) de la válvula 1/2” transparente/rojo solenoide (Fig. 6) Potter Electric Signal Company, LLC • San Luis, Misuri, EE.UU. • Teléfono: 800-325-3936 • www.pottersignal.com • 5401590 - REV. A 1/20 PÁGINA 8 DE 12...
  • Página 9 Nota: Ver las figuras 1 y 2 para ejemplos de uso de la extensión 20. Vuelva a poner la tapa de la caja del interruptor RBVS y apriete de soporte. firmemente los tornillos de la tapa a 10  lb-in (1.13  N·m) como mínimo.
  • Página 10: Montaje Alternativo En Válvula Con Manija Tipo Palanca

    12. Retire la tapa de la caja del interruptor RBVS. manija tipo palanca 13. Deslice la caja del RBVS por el soporte en “L” hasta que haga contacto con la manija en T de la válvula. Apriete firmemente los dos tornillos antivandalismo. esto garantizará que el actuador Figura 3 quede completamente oprimido.
  • Página 11: Instalación En Válvula Solenoide

    “L”. GOMA (PEQUEÑO) (2) 14. Deslice el RBVS por el soporte en “L” de modo que el actuador se active con el perno de la bobina de la válvula solenoide. 15. Sostenga la caja del RBVS hacia abajo para que el actuador quede...
  • Página 12: Especificaciones De Ingeniería

    SPDT con capacidad nominal de 10.1 a a 125 V Ca y de 2 a a 30 V CC. el interruptor de supervisión de la válvula de bola debe ser del modelo RBVS, tal como viene fabricado por potter electric Signal Company LLC.