4.5.1
General
Ensure that the following general requirements are met for safe and reliable operation of the cooling units:
•
Choose an installation site for the switch cabinet that ensures adequate ventilation of the cooling unit. The minimum
distance of units from each other and from the wall is 200 mm.
•
Installations in the switch cabinet must not obstruct air circulation.
•
Secure switch cabinet against tilting.
•
Make sure that any hinges can bear the extra weight with cooling unit.
•
The cooling unit can be installed with or without an external unit cover.
•
Protect the installation site from heavy soiling using covers.