4.2
Air damper setting
The regulation of the air-rate is made by adjusting the air damper (1)
Fig. 11, after loosing the screws (2).
When the optimal regulation is reached, screw tight the screws (2).
4.3
Combustion check
CO
It is advisable to not exceed 10% of CO
2
to avoid the risk that small changes of the adjustments due, for
instance, at draught variation, may cause combustion with
insufficient air and consequently formation of CO.
CO
Not exceeding 100 mg/kWh (93 ppm).
IONIZATION CURRENT
The minimum current necessary for the
control box operation is 3 µA.
The burner normally supplies a higher cur-
rent value, so that no check is needed.
However, if you want to measure the ioni-
zation
current,
you
connector fitted to the red wire and insert a
microammeter.
4.4
Burner start-up cycle
Normal
Thermostat
Motor
Ignition transformer
Valves
Flame
Lock-out
max. 2s
When flame-failure occurs during working, shut down takes place within one second.
20008491
(natural gas), in order
2
must
open
the
40s
Terminal board
of control-box
10
Lock-out, due to ignition failure
max. 2s
8
GB
2
D5231
Connector
D5006
40s
3s
1
2
Fig. 11
Probe
Fig. 12
D4172
Fig. 13