WARNING
Definition of warning signs :
CAUTION
: This pump has been evaluated for use with water only.
WARNING
: Disconnect electrical power before working on the unit !
AREA OF APPLICATION
1
SANICONDENS
Best Flat is a pump used to lift
®
condensation water from an air conditioning system, a
condensation boiler, dehumidifiers or from refrigeration
units. It includes a neutralization compartment where
granules are added to neutralize acidic condensate.
Many local and state codes require the condensate to be
neutralized prior to being discharged.
The pump starts automatically and has a high level of
performance, safety and reliability as long as all the
installation and maintenance instructions mentioned in
this manual are strictly followed.
All applications other than those described in this
manual are prohibited.
DESCRIPTION
2
2.1 OPERATING PRINCIPLE
SANICONDENS
Best Flat contains a pump. The tank
®
of the SANICONDENS
®
which controls the operation of the motor. When the
condensate enters the tank, the pump starts up.
SANICONDENS
Best Flat has also a built-in
®
secondary float that can trigger an alarm (audible and/
or visual) and a condensate neutralization system.
2.2 TECHNICAL DATA
Type
Max. vertical pumping
Maximum flow rate
Min. pH
Level ON/OFF
Voltage
Frequency
Current consumption
Electrical class
Protection index
Sound level
Average operating
temperature
Maximum allowable
temperature
Weight
Tank volume
Supply cable
Discharge hose
Alarm cable (2 cores)
Max. power for the
connected boiler
Wall mounting
Risk of electrical shock.
Risk of machinery breakdown or its operation.
Directions to be used only by qualified professionals.
Best Flat has a built-in a float
CD 10
15 Ft (4.5 m)
100 gal/h
2.5
2.2 in/ 1.8 in (56/46 mm)
115 V
60 Hz
1.6 A
I
IP20
< 45 dBA
95°F (35°C)
176°F (80°C)
S3 15%
(1min30 ON/8min30 OFF)
4.4 lb (2 kg)
0.9 gal (3.5 L)
4.9 Ft (1.5 m)
16.4 Ft (5 m),
Øint : 3/8'' (10 mm)
4.9 Ft (1.5 m)
500,000 BTU
Yes
2.3 LIST OF PARTS SUPPLIED : see pg. 1
2.4 DIMENSIONS : see pg. 6
2.5 PERFORMANCE CURVES : see pg. 6
2.6 VERTICAL PUMPING/HORIZONTAL
PUMPING : see pg. 6
START UP
3
3.1 INSTALLATION
Always install the pump :
- horizontally, using a leveling tool,
- as close as possible to the appliance keeping in
mind that the condensate has to drain through
gravity into the pump.
To ensure proper ventilation of the motor, the
pump must be free of any obstruction.
The pump can be mounted against a wall using the
wall bracket provided:
- Fix the wall bracket C horizontally with the plastic anchors
A and screws B supplied (accessory bag). See fig. 1 and 2.
- Snap the SANICONDENS
bracket. See fig. 3A and 3B.
- Check that the SANICONDENS
leveled (fig. 3C
).
3.2 HYDRAULIC CONNECTION
Connecting the inlets
The pump has two inlets that can be used as required.
- The upper inlet is open. If used (fig. 5), close the
lower side inlet with the supplied gasket G, cover H
and nut E (fig. 4.2).
Do not use the closed upper inlet.
- To use the lower side inlet (fig. 4.1), place the nut E
and Ø1'' F or 1¼'' G gasket on the inlet pipe and screw
it onto the inlet.
Drain the condensate water to any of these inlets. If
necessary, use the rubber flexible adapter D (fig. 5).
Connecting the discharge pipe
The SANICONDENS
connection must be connected to the flexible hose I.
- Unroll the flexible vinyl hose I.
- Insert the hose into the discharge connection that has
a built-in non-return valve (see fig. 6).
- Position the flexible hose in the upmost vertical
position possible to avoid any kinking. It is
recommended to make a smooth turn to avoid the
hose from kinking.
- Secure the hose by using the clamp supplied J (fig 6).
The 3/8'' vinyl hose can be connected to a PVC pipe of
larger diameter by using the plastic reducer coupling K
(provided). Provide a cable tie to secure the connection
(fig. 6.1 and 6.2 ).
The SANICONDENS
return valve to prevent re-activation.
7
Best Flat onto the
®
Best Flat is
®
Best
Flat discharge
®
Best Flat is fitted with a non-
®