11. TECHNICAL INFORMATION
The Watchman Sonic Advanced is suitable for use in tanks for the
storage of diesel, water, fuel, kerosene, and gas oil types A2, C1, C2
and D as defined by BS 2869. Check with the manufacturer and/or
supplier before using with any other fluids. In the event of a power
failure or if the receiver is switched off or moved to a new socket:
When power returns again or unit is switched on, the receiver display
screen will show the top bar flashing. There is no need to repeat
the matching instruction. The top bar will continue to flash for 2
minutes, after which time the last valid signal is displayed. It may
take up to two hours for the next transmission from the transmitter.
CHANGING BATTERY
Please note opening the unit will potentially affect the
lifespan of the unit.
Under Warranty
If a unit is still under warranty and is clearly showing low battery
symbol (Shown in picture 16), please contact our Watchman
helpline. Units under warranty SHOULD NOT BE OPENED.
Warranty will be void if unit is opened within the warranty period.
Out of Warranty Only
Though the lithium battery will have a very long service life, it will
eventually become exhausted and will need replacing.
We recommend using Varta CR2430.
• Remove transmitter from tank
• Take transmitter indoors, into a clean dry environment
• Using a cross point screwdriver, undo the four screws,
located under the main body of transmitter
• Remove the top cover
• Gently slide battery out from under battery holder clip
• Gently slide battery into battery holder taking care not to
bend battery holder clip
• Re-fit cover
• Evenly tighten all four screws - do not over tighten
• Pair up transmitter and receiver by following Point 6 again
• Replace transmitter on the tank
If the receiver detects a low battery the following warning
message is displayed on the LCD. The level of oil in the tank plus
a constantly flashing warning triangle. (Shown in picture 16)
GUARANTEE
The Watchman Advanced has a warranty period of 1 year. For each
product accepted by Kingspan Water & Energy as warrantable,
Kingspan Water & Energy will rework or replace the product and
return to the customer at Kingspan Water & Energy expense. The
warranty becomes invalid if the sealed unit is opened (Part D).
Kingspan Water & Energy will not warrant products that have been:
• Used outside the functional and Water & Energy conditions for
which they were designed.
• Physically abused, incorrectly handled/ installed or damaged
in transit.
• Purchased over 1 year ago. (Proof of purchase will be required).
• Returned to Kingspan Water & Energy in a form other than in
which they were originally supplied.
• Subjects to "Act of God", e.g.: lightning strike, flood or any other
catastrophic event beyond Kingspan Water & Energy's control.
6
!
!
LOW BATTERY
TRANSMISSION
16
NOT HEARD
Leak Detection: If the leak is detected
(Watchman Sonic Advanced Plus version)
buzzer beeps every 10s. Please check
the tank (bund). False alarms can be
caused by damaged cable or incorrect
installation.
TRANSMISSION NOT HEARD
If the receiver detects a transmission not heard for a long time
the symbol outlined in Pic 17 is displayed on the LCD. This starts
approximately 24 hours from the last received good signal.
(Shown in picture 16). To rectify this re-site the receiver
in a location where the transmission is heard. Rematch r
eceiver and transmitter as per point 7.
NO ECHO CONDITION
If the receiver detects a No Echo Condition the following message
is displayed on the LCD. Warning triangle constantly flashing
plus indication bar 5 on. (Shown in picture 18). To rectify this
situation check that the transmitter unit is correctly positioned
on the tank and no interference is present from a tank wall,
corrugation or window.
FALSE ALARM
False alarms may be caused by poor installation of the unit on
the tank. Please ensure that the unit is sitting correctly on the
tank with the correct amount of clearance each side of it to the
bottom of the tank. (See section 2).
Ensure that the tank is not prone to vibration by the wind or
passing traffic. Sudden ripples of the fluid in the tank caused by
vibrations may cause false alarms. Check the tank is sitting level
on a stable base
Any sensor product deemed damaged by the customer shall be
returned to Kingspan Water & Energy's facility at the customer's
expense. Kingspan Water & Energy shall not be liable for any costs
in relation to the returned products.
The purchase invoice and a description issue should be joined with
the faulty product. The product should be returned at your shop
or directly at the following address:
REGISTER GUARANTEE ONLINE:
kingspanwaterandenergy.com/warranty
Kingspan Water & Energy Ltd, 180 Gilford Road, Portadown,
Co. Armagh, Northern Ireland BT63 5LF.
Each faulty product must receive Kingspan Water & Energy's
After-Sale-Service approval before being returned.
!
NO ECHO
17
18
CONDITION
SUDDEN DROP
19
ALERT