APPENDIX
APPENDIX - TECHNICAL SPECIFICATIONS
P047
0
Out of CONFIG status. The HMI and parameters P006 and P680 must not indicate ConF
1
Two or more DIx (P263...P266) programmed for (4 = Forward Run)
2
Two or more DIx (P263...P266) programmed for (5 = Reverse Run)
3
Two or more DIx (P263...P266) programmed for (6 = Start)
4
Two or more DIx (P263...P266) programmed for (7 = Stop)
5
Two or more DIx (P263...P266) programmed for (8 = Direction of Rotation)
6
Two or more DIx (P263...P266) programmed for (9 = LOC/REM)
7
Two or more DIx (P263...P266) programmed for (11 = Accelerate E.P.)
8
Two or more DIx (P263...P266) programmed for (12 = Decelerate E.P.)
9
Two or more DIx (P263...P266) programmed for (14 = 2
10
Reserved
11
Two or more DIx (P263...P266) programmed for (24 = Disable Flying Start)
12
Two or more DIx (P263...P266) programmed for (26 = Programming Off)
13
Reserved
14
Reserved
15
DIx (P263...P266) programmed for (4 = Forward Run) without DIx (P263...P266) programmed for (5 = Reverse Run) or the
opposite
16
DIx (P263...P266) programmed for (6 = Start) without DIx (P263...P266) programmed for (7 = Stop) or the opposite
17
P221 or P222 programmed for (8 = Multispeed) without DIx (P263...P266) programmed for (13 = Multispeed) or the opposite
18
P221 or P222 programmed for (7 = E.P.) without DIx (P263...P266) programmed for (11 = Accelerate E.P) or the opposite
19
P224 programmed for (1 = DIx) OR P227 programmed for (1 = DIx) without DIx (P263...P266) programmed for (1 = Run/Stop)
AND without DIx (P263...P266) programmed for (2 = General Enable) AND without DIx (P263...P266) programmed for (3 =
Quick Stop) AND without DIx (P263...P266) programmed for (4 = Forward Run) AND without DIx (P263...P266) programmed
for (6 = Start)
20
Reserved
21
P221 or P222 programmed for (8 = Multispeed) with DI1 (P263) AND DI2 (P264) programmed for (13 = Multispeed)
22
Minimum Frequency Reference (P133) greater than Maximum Frequency Reference (P134)
23 to 28
Reserved
29
Two or more DIx (P263...266) programmed for (49 = Enable Fire Mode) OR two or more DOx (P275...P283) Programmed for
(45 = Fire Mode OR P580 programmed for 1, 2 or 4 (Fire Mode Enabled) without DIx programmed for (49 = Enable Fire Mode)
OR DIx programmed for (49 = Enable Fire Mode) OR DOx programmed for (47 = Fire Mode) and P580 programmed for (0 =
Fire Mode Disabled) or (3 = Reserved)
30 to 32
Reserved
33
Parameterization in conflict with DC Bus Compensation. Energy Saver active (P588 value other than zero), Controle VVW ativo
(P202 = 5), Functions Ride-Through or Flying Start are enable (P320 value other than zero)
16 | WECC300
Table 1.1: Situations for CONFIG status
nd
Table 1.2: Levels of performance monitoring of the DC link voltage
Supply
200 to 240 Vac (P296 = 2)
Table 1.3: Overtemperature actuation levels of the power module
Line
Frame Size
Level A050
200 V
A
90 °C (194 °F)
Condition
Ramp)
Level F021
Level F022
200 Vdc
410 Vdc
Level F051
100 °C (212 °F)