QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS
Param.
Description
P230
Dead Zone (FI1 )
P245
FI1 Filter
P246
FI1 Input Function
P247
FI1 Input Gain
P248
FI1 Minimum Input
P249
FI1 Input Offset
P250
FI1 Maximum Input
P263
DI1 Input Function
P264
DI2 Input Function
P265
DI3 Input Function
P266
DI4 Input Function
8 | WECC300
Adjustable Range
0 = Off
1 = On
0.00 to 16.00 s
0 = Off
1 = Active in DI1
2 = Active in DI2
3 = Active in DI3
4 = Active in DI4
0.000 to 9.999
1 to 3000 Hz
-100.0 to 100.0 %
1 to 3000 Hz
0 = Not Used
1 = Run/Stop
2 = General Enable
3 = Quick Stop
4 = Foward Run
5 = Reverse Run
6 = 3-Wire Start
7 = 3-Wire Stop
8 = Direction of Rotation
9 = LOC/REM
10 = JOG
11 = Accelerate E.P.
12 = Decelerate E.P.
13 = Multispeed
14 = Ramp 2nd
15 to 17 = Not Used
18 = No Ext. Alarm
19 = No Ext. Fault
20 = Reset
21 to 23 = Not Used
24 = Disab. Flying Start
25 = Not Used
26 = Progr. Off
27 to 31 = Not Used
32 = 2nd ramp Multispeed
33 = 2nd ramp Increase EP
34 = 2nd ramp Decrease EP
35 = 2nd ramp FWD Run
36 = 2nd ramp REV Run
37 = Start / Inc. EP
38 = Dec. EP / Stop
39 = Stop
40 = Safety Switch
41 = Application Fuction 1
42 = Application Fuction 2
43 = Application Fuction 3
44 = Application Fuction 4
45 = Application Fuction 5
46 = Application Fuction 6
47 = Application Fuction 7
48 = Application Fuction 8
49 = Enable Fire Mode
50 to 54 = Not Used
See options in P263
See options in P263
See options in P263
Factory Setting
Prop.
0
cfg
0.00 s
0
cfg
1.000
100 Hz
0.0 %
1000 Hz
1
cfg
8
cfg
0
cfg
0
cfg