QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS
Param.
Description
P080
Last Fault on Fire Mode
P081
Second Fault on Fire Mode
P082
Third Fault on Fire Mode
P100
Acceleration Time
P101
Deceleration Time
P102
Acceleration Time 2nd Ramp
P103
Deceleration Time 2nd Ramp
P104
Ramp S
P105
1st / 2nd Ramp Selection
P106
Emerg. R. Acceleration Time
P107
Emerg. R. Time Deceleration
P120
Speed Ref. Backup
P121
Reference via HMI
P122
JOG Reference
P124
Multispeed Ref. 1
P125
Multispeed Ref. 2
P126
Multispeed Ref. 3
P127
Multispeed Ref. 4
P128
Multispeed Ref. 5
P129
Multispeed Ref. 6
P130
Multispeed Ref. 7
P131
Multispeed Ref. 8
P133
Minimum Frequency
P134
Maximum Frequency
P135
Maximum Output Current
P136
Manual Torque Boost
P137
Automatic Torque Boost
P138
Slip Compensation
P139
Output Current Filter
P140
Slip Com. Filter
P142
Maximum Output Voltage
P143
Intermediate Output Voltage
P145
Field Weakening Speed
P146
Intermediate Frequency
P149
DC Link Comp. Mode
P150
DC/LC Regul. Type
P151
DC Link Regul. Level
P156
Rated Speed Overload Current
P157
Overl. Curr. 50 % Speed
P158
Overl. Curr. 20 % Speed
P178
Rated Flux
P200
Password
P202
Type of Control
6 | WECC300
Adjustable Range
0 to 999
0 to 999
0 to 999
0.1 to 999.9 s
0.1 to 999.9 s
0.1 to 999.9 s
0.1 to 999.9 s
0 = Off
1 = Active
0 = First Ramp
1 = Second Ramp
2 = DIx
3 = Serial/USB
4 to 5 = Reserved
6 = SoftPLC
0.1 to 999.9 s
0.1 to 999.9 s
0 = Off
1 = On
2 = Backup by P121
0.0 to 400.0 Hz
-400.0 to 400.0 Hz
-400.0 to 400.0 Hz
-400.0 to 400.0 Hz
-400.0 to 400.0 Hz
-400.0 to 400.0 Hz
-400.0 to 400.0 Hz
-400.0 to 400.0 Hz
-400.0 to 400.0 Hz
-400.0 to 400.0 Hz
0.0 to 400.0 Hz
0.0 to 400.0 Hz
0.0 to 40.0 A
0.0 to 30.0 %
0.0 to 30.0 %
-10.0 to 10.0 %
0.000 to 9.999 s
0.000 to 9.999 s
0.0 to 100.0 %
0.0 to 100.0 %
0.0 to 400.0 Hz
0.0 to 400.0 Hz
0 = Off
1 = Normal
2 = Overmodulation
3 = Extended
0 = hold_Ud and desac_LC
1 = acel_Ud and desac_LC
2 = hold_Ud and hold_LC
3 = acel_Ud and hold_LC
325 to 460 V
0.1 to 40.0 A
0.1 to 40.0 A
0.1 to 40.0 A
50.0 to 150.0 %
0 = Inactive
1 = Active
2 to 9999 = New Password
0 = V/f
1 = V/f Quadratic
2 to 4 = Not Used
5 = VVW
Factory Setting
Prop.
ro
ro
ro
5.0 s
10.0 s
5.0 s
10.0 s
0
cfg
0
5.0 s
5.0 s
1
3.0 Hz
5.0 Hz
3.0 Hz
10.0 (5.0) Hz
20.0 (10.0) Hz
30.0 (20.0) Hz
40.0 (30.0) Hz
50.0 (40.0) Hz
60.0 (50.0) Hz
66.0 (55.0) Hz
3.0 Hz
66.0 (55.0) Hz
1.5 x I
V/f
nom
According to the
V/f
Inverter Model
0.0 %
V/f
0.0 %
V/f
0.050 s
V/f, VVW
0.500 s
VVW
100.0 %
cfg, V/f
50.0 %
cfg, V/f
60.0 (50.0) Hz
cfg, V/f
30.0 (25.0) Hz
cfg, V/f
0
cfg, V/f
0
cfg, V/f, VVW
380 V (P296 = 2)
V/f, VVW
1.2 x I
nom
1.2 x I
nom
1.2 x I
nom
100.0 %
VVW
0
cfg
0
cfg