Error #32: EMPTY EXTERNAL BOTTLE: error message appears during the process of filling
the refrigeant bottle when the pressure drops to zero before the completion of the procedure
Solution: Check the connections, quick couplers and valves on the external bottle; if the
external bottle is empty, replace it with a full one, then run another filling.
Error # 33: HIGH PRESSURE ALARM: error message appears during the recovery
procedure, internal bottle filling, emptying hoses, flushing hoses or A/C system flushing, this
occurs when the hydraulic pressure reaches approximately 20 bar. The causes may be:
Ambient temperature where is located in the station is too high. Solution to wait for a
sufficient time to cool the charging station before resuming the interrupted procedure.
Number of services performed by the station is excessive. Solution to wait for a
sufficient time to cool the charging station before resuming the interrupted procedure.
One of the taps of the internal bottle is closed. Solution to open the tap and resume the
interrupted procedure.