Electronic Device Description (EDD)
• You can locate the EDD in Device Catalog, under Sensors/Level/Echo/Siemens/SITRANS
LR200.
• Check the product page of our website at:
www.siemens.com/LR200, under Downloads, to make sure you have the latest version of
SIMATIC PDM, the most recent Service Pack (SP) and the most recent hot fix (HF). If you
need to install a new EDD see
Configuring a new device
: Clicking on Cancel during an upload from device to SIMATIC PDM will cause some
Note
parameters to be updated.
1)
Check that you have the most recent EDD, and if necessary download it from the product
page listed above. Save the files to your computer, and extract the zipped file to an easily
accessed location. Launch SIMATIC PDM – Manager Device Catalog, browse to the
unzipped EDD file and select it.
2)
Launch SIMATIC PDM and create a new project for LR200. Application Guides for setting
up PROFIBUS PA devices with SIMATIC PDM can be downloaded from the product page
of our website at: www.siemens.com/LR200.
3)
Upload parameters to the PC/PG.
4)
Configure the device via the Quick Start wizard (see below).
Quick Start Wizard via SIMATIC PDM
Notes:
• The Quick Start wizard settings are inter-related and changes apply only after you click on
Transfer at the end of step 5.
• Each time the Quick Start Wizard is initiated, the start-up settings are factory defaults.
The Wizard will not recall previous user-defined settings.
• Click on BACK to return and revise a setting or Cancel to exit the Quick Start.
Launch SIMATIC PDM, open the menu Device – Quick Start, and follow steps 1 to 5.
7ML19985XD81
SITRANS LR200 (PROFIBUS PA) – QUICK START MANUAL