9. Control Panel

9.3.5 Measurement Screen

Use "Down/Right" key to select "MEASUREMENT" option. Press "Enter" key to enter Control sub-menu. Select MASTER#00 (Module ID), as
defined from table 7.1, to view Input, Output, Bypass, Load and Battery status for each module.
HOME
Input
Input
Output
Output
Bypass
Bypass
Load
Load
16-11-183-9334F8.indb 22
MENU
Input phase voltage (L1, L2, L3), Unit 0.1V
L-N Voltage (V)
Input frequency (L1, L2, L3), Unit 0.1Hz
Frequency (Hz)
Output phase voltage (L1, L2, L3), Units 0.1V
L-N Voltage (V)
Output phase current (L1, L2, L3), Units 0.1A
L-N Current (A)
Output frequency (L1, L2, L3), Units 0.1Hz
Frequency (Hz)
Output power factor (L1, L2, L3), Units 0.00
Power Factor
Bypass phase voltage (L1, L2, L3), Unit 0.1V
L-N Voltage (V)
Bypass frequency (L1, L2, L3), Units 0.1Hz
Frequency (Hz)
Bypass power factor (L1, L2, L3), Units (NA)
Power Factor
Apparent power, Units 0.1kVA
S Out (kVA)
Actual power, Units 0.1kW
P Out (kW)
Percentage of the UPS rating load, Units 1%
Load Level (%)
MEASUREMENT
MASTER#00
STS #
System ID
22
Input
Output
Bypass
Load
Battery
1/18/2017 9:53:22 AM

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido