KPHA-DUO
Mechanical daily time switch for DIN rail
4. Setting the time
Open the transparent cover
Turn the dial clockwise till the arrow indicates the actual time
Set the groove in the rotating dial on the actual minutes
N.B.: Turn the dial using a screwdriver or pencil and rotate clockwise. Do not act directly on the dial
5. Time setting
Daily: Grey tappets for the night-Green tappets for the day
The 48 tappets have 2 possible positions:
Position 1: insert-push the tappet till stops
Position 2: remove-pull the tappet out
MINIMUM ON/OFF SETTING
Daily: 30 munutes
Weekly: 3.5hours.
6. Securing the device
The transparent cover can be sealed sliding a sealing wire through the pre-set holes. The terminal covers can be
sealed as well.
7. Reserve
N.B.: The time switch will start operating approx. 5miutes after connecting the mains.
After approx.60 hours of working the time switch reaches its complete charge reserve of 150 hours.
www.grupotemper.com