3.14 Digital input configuration
If the digital input is configured as an immediate alarm A4 = 1/2 the compressor is controlled according to
parameter A6.
Cod.
Parameter
A4
Digital input 1 configuration (DI1)
1 = immediate external alarm
2 = delayed external alarm
A5
Digital input 2 configuration (DI2)
See A4
A6
Stop compressor on external alarm
0 = compressor always off ;
100 = compressor always on
A7
Digital alarm input delay
0 = control outputs unchanged
3.15 Frost protection alarm
The probe has to be set as a frost protection probe, see parameter list and diagram below.
If this probe measures a temperature less than the threshold ALF for a time greater than AdF, the alarm "AFr"
(manual reset) is activated and the Fullmotion compressor is switched OFF.
Cod.
Parameter
Probe 2 configuration (S2)
0 Absent
1 Product (display only)
/A2
2 Defrost
3 Condenser
4 Frost
Probe 3 configuration (S3/ DI1) see /A2
/A3
0 = Digital input 1
Probe 4 configuration (S4/ DI2) see /A2
/A4
0 = Digital input 2
ALF
Frost protection alarm threshold
AdF
Frost protection alarm delay
Alarms involved
Cod.
Message
AFr
Frost protection alarm
ir33+ wide Fullmotion - +040000055 - rel. 1.0 - 09.06.2014
UOM
-
-
Min
Min
S
ALF
ALARM
ON
AFr
OFF
Fig. 3.g
UOM
-
-
-
°C/°F
Min
Dis.
Type
C
I
C
I
C
I
C
I
AdF
Dis.
Type
C
I
I
C
I
C
C
I
C
I
16
Def.
Max
Min
0
14
0
0
14
0
0
100
0
0
250
0
t
t
Def.
Max
2
4
0
4
0
4
-28
200
1
15
Tab. 3.l
Min
0
0
0
-50
0
Tab. 3.m