FWL+FWR
FWM+FWS
Read this manual attentively before starting up the unit. Do
Improper installation or attachment of equipment or
accessories could result in electric shock, short-circuit,
designed for the use with the equipment and have them
installed by a professional.
If unsure of installation procedures or use, always contact
your Daikin dealer for advice and information.
The optional EEH (electric heater kit) cannot be mounted on
units which are set up for 2-pipe systems with 4-row coil and
4-pipe systems.
Β
ΕΦΟΡΕ ΙΝΣΤΑΛΛΑΤΙΟΝ
Installation and maintenance should be carried out by technical
per
safety regulations.
When receiving the unit please check its state, verifying if any damage
occurred during the transport.
Refer to the relevant technical sheets for installation and use of
possible accessories.
Identify model and version of the unit from the indications stated on the
carton package.
Υ
ΣΕ ΑΝD ΟΠΕΡΑΤΙΝΓ ΛΙΜΙΤΣ
Daikin shall not be held liable
-
- if the unit has been used improperly,
- if the unit has been used under conditions that are not permitted,
-
carried out,
- if non original spare parts have been used.
Keep the unit in its packaging until it is ready to be installed, to prevent
dust getting inside.
Operating limits are shown here below; all other uses are considered
improper:
!
!
water temperature: 5°C~95°C
!
maximum operating pressure: 10 bar
!
air temperature: 5°C~43°C
!
nominal power supply voltage: 230V - 50 Hz
!
ambient air humidity limit: RH<85% non-condensing
Selection of location:
Equipment designed for ambient air conditioning and intended for use
in civil comfort applications.
!
present
!
do not let water spray directly on the unit;
!
install the unit on ceilings or walls that bear its weight. Leave
enough space all around for proper operation and maintenance of
the unit, taking into account all installed optional accessories.
!
never place the heating unit immediately under an electric
plug-socket.
Installation and operation manual
1
Fan coil units
D
ΙΜΕΝΣΙΟΝΣ
1
Clear space for hydraulic connections
2
3
Clear space for electric connections
4
Hydraulic connections (4 DF = 4 pipe system)
5
Condensate drainage for vertical installation
6
Air outlet for concealed models
7
Air suction for concealed models
8
Condensate draining for horizontal installation
9
Air outlet
10
Air inlet
(*)
Indications applicable to units with hydraulic connections on the left side; in case of right side
connections the indications for "clear space" are reversed.
Ι
ΝΣΤΑΛΛΑΤΙΟΝ
Before installing the fan coil, ensure that:
-
device and for performing installation and maintenance (respect
- The air inlet and delivery are not obstructed.
- The hydraulic connections are positioned and dimensioned as
- The electric power supply line has the features requested on the
fan coil's data plate.
In normal operation, particularly with the fan at minimum speed and
ambient air with high relative humidity, condensation may form on
the air outlet and on some external parts of the unit. To avoid such
issues while always remaining within the operating limits envisaged
for the unit, it is necessary to limitthe (average) temperature of the
water inside the heat exchanger. In particular, the difference
between the air dew point (TA,DP) and the average water
temperature (TWM) must NOT exceed 14 °C, according to the
following relationship:
TW>TA,DP-14 °C
Example: in the case of ambient air at 25 ° C with 75% relative
humidity, the dew point temperature is about 20 ° C and therefore
the average temperature of the water
in the battery must be greater then:
-20-14 = 6 °C in order to avoid condensation on a fancoil equipped
with a valve.
- 20-12 = 8 °C If the valve kit accessory can not be installed.
In the event the indoor unit is stopped for a prolonged period, with
the fan stopped and circulation of cold water in the heat exchanger,
condensation may also form on the unit's exterior. In this case it is
advisable to install the 3-way (or 2-way) valve
is stopped.
Remove the cabinet, where existing, by unscrewing the 4 fastening
FWL and FWR versions, also unscrew the 2 screws on the front panel.
and the supplied anchor screws, keeping the unit at least 100 mm
models FWM, FWS, FWL and FWR verify that the installation height
installation heights we suggest to proceed with the back suction from
Installation and
operation manual
(*)
(*)
FWV+FWZ+FWL+FWR+FWM+FWS
Fan coil units
4PW17548-5