Descargar Imprimir esta página

PowerWalker VI CW Serie Guía Rápida página 6

Ocultar thumbs Ver también para VI CW Serie:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 26
ENGLISH
VII.
UPS Settings
Parameter 1
Output voltage setting
01
Programmable outlets
02
Settings of programmable outlets
03
This is reserved position, changing the value will not have any effect
04
Limitation setting for autonomy time 0-999/dIS
06
This is reserved position, changing the value will not have any effect
07
EPO logic setting
08
Exit Settings
00
VIII.
Programmable Outlets
The settings can be only changed in Standby Mode. After you setting the time limit, Exit the
Settings (Menu 00) and disconnect input, wait until it shuts off completely. Settings will be
saved after the UPS is turned on again.
IX.
Site Wiring Fault
"Site Wiring Fault" can be disabled via software. Please check software manual for details.
X.
Technical Specification
MODEL
POWER*
INPUT
Acceptable Voltage
Frequency Range
OUTPUT
Output voltage
AC
Voltage
Regulation
Frequency
Synchronized
Range
Frequency Range
AVR boost/buck
Current Crest Ratio
208/220
/230/240
ENA/dIS
0-999
AO
AC
VI 1100 CW
VI 1500 CW
1100VA/770W
1500VA/1050W
50/60 Hz ± 5 Hz (auto sensing)
47 ~ 53 Hz or 57 ~ 63 Hz
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode)
-10%/+16% at 208V; -15%/+10% at 220V;
-15%/+10% at 230V; -15%/+10% at 240V
Parameter 2
Value in V AC
Enable or Disable (default).
Backup time limit for programmable outlets
(default 999)
Limit in minutes; 0 actually means 10s
Normally Open (default). EPO will be activated
if pins 1 and 2 are not shorted
Normally Closed. EPO will be activated if pins 1
and 2 are shorted
VI 2000 CW
2000VA/1400W
162-290 VAC
208*/220/230/240VAC
± 1.5% (Batt. Mode)
3:1
VI 3000 CW
3000VA / 2100W

Publicidad

loading