Installation
CAUTION
Strictly comply with the following rules to prevent damage of the
indoor units and human injury.
• Do not put a heavy article on the indoor unit or let a person get on it.
(Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the
indoor unit unpacked by necessity, use buffering cloth or other
material not to damage the unit.
External dimensions
Some models have no
drain guard here.
80
100
90 knockout hole
(For air taking-in)
EN-15
A
Hanging bolt pitch
B
Unit external dimension
C
(Outside)
Electrical control box
– 8 –
• To move the indoor unit, hold the hooking brackets (4 positions) only.
• Do not apply force to the other parts (refrigerant pipe, drain pan,
foamed parts, resin parts or other parts).
• Hanging bolt pitch of air intake chamber side is different (centre
position), make sure not to make mistake to install the setting direction.
• Carry the package by two or more persons, and do not bundle it with
plastic band at positions other than specified.
• To install vibration isolation material to hanging bolts, confirm that it
does not increase the unit vibration.
Hanging bolt
25
or less
(Only the position of
an access cover.)
Access cover
187
Refrigerant pipe
155
connecting port
58
(Liquid side)
35
Drain pipe
connecting port
Refrigerant pipe
connecting port
(Gas side)
37
173
Wires
drawing-out port
Installation Manual
(Unit: mm)
Model type
A
B
C
07,10,13 type
770
700
650
16 type
970
900
850
22,24 type
1,170
1,100
1,050
EN-16