Rated Motor Speed
P0311
Nominal motor speed (rpm) from rating plate
0 - 40000 1/min
P0700
Selection of Command Source
(on / off / reverse)
1 = BOP
2 = Terminal / Digital Inputs (default)
Selection of Frequency Setpoint
P1000
1 = BOP
2 = Analogue Setpoint (default)
Min. Motor Frequency
P1080
Sets minimum motor frequency
(0 - 650 Hz) at which the motor will run
irrespective of the frequency setpoint. The value
set here is valid for both clockwise and anti-
clockwise rotation
Max. Motor Frequency
P1082
Sets maximum motor frequency (0 - 650 Hz) at
which the motor will run at irrespective of the
frequency setpoint. The value set here is valid
for both clockwise and anti-clockwise rotation.
Now limited to 550 Hz, see FAQ 101935922.
26
English
MICROMASTER 420/430/440, Getting Started Guide 10/14 - A5E02779537A3
Deutsch
Motornenndrehzahl
Motornenndrehzahl (1/min) vom Typenschild
Wahl von Befehlsquellen
(EIN / AUS / Richtungsumkehr)
1 = BOP
2 = Klemmen (Werkseinstellung)
Wahl des Frequenzsollwerts
1 = BOP
2 = Analogsollwert (Werkseinstellung)
Minimal Motorfrequenz
Stellt die minimale Motorfrequenz
(0 - 650 Hz) ein, mit der der Motor unabhängig
vom Frequenzsollwert läuft. Der hier
eingestellte Wert gilt für beide Drehrichtungen
Maximal Motorfrequenz
Stellt die höchste Motorfrequenz (0 - 650 Hz) ein,
mit der der Motor unabhängig vom
Frequenzsollwert läuft. Der hier eingestellte Wert
gilt für beide Drehrichtungen.
Jetzt auf 550 Hz begrenzt, siehe FAQ
101935922.