3.8
Electrical connection
The appliance must be connected by a professional in compliance with the French standard NFC 15-
100.
This step must only be done when the other installation steps are finished. This avoids any risk of
electric shocks when installing the various parts of the system.
The VMI® unit must be connected to a dedicated line. On the switchboard, the installation must be
equipped with a 16 A bipolar circuit breaker, a 30 mA differential circuit breaker and a means for
disconnecting in the fixed line.
Connect the supplied cable to the mains via a sealed junction box (not supplied).
Connect the URBAN VMI® to the mains power via the junction box after removing the power access
hatch.
Type of cable: 3 x 1.5 mm² with ground conductor.
Single phase 230 VAC, 50 Hz
Brown
Yellow/Green
3.9
Remote control
If the premises are equipped with a heating thermostat, the remote control should preferably be
placed next to it. If not, it should be placed in a living area, as it measures the relative ambient humidity
and controls the ventilation flow rate. It must never be placed above a radiator, close to a source of
cold, under a ventilation opening or closed in a cupboard or drawer.
The remote control can either be placed on a horizontal surface or fixed to the wall via the 2.5 mm
diameter hole on the back of the remote control.
Yellow/Green
Blue
Brown
Blue
Sealed box
Phase
Ground
Neutral
53