Table 2-2 Main tubing size after distriburion (D2, D3, Dn)
Outdoor
Outdoor tubing (mm)
unit
Suction tube
45.0 kW
Discharge tube
Liquid tube
Suction tube
56.0 kW
Discharge tube
Liquid tube
Suction tube
71.0 kW
Discharge tube
Liquid tube
*1
If anticipating future expansion, select tube diameters according to total capacity after expansion.
*2
If the maximum tubing length exceeds 90 m (equivalent length), increase the diameter of the main tubing to the size
in ( ) for both liquid and gas tubes. However, gas tube diameter should not exceed 31.75 mm. (Reducers are available
locally.)
*3 "–* *" in the table above means "** kW or less"
Table 2-3 Branching⇔solenoid valve kit tubes<3-tube side>
Tubing size (mm)
Table 2-4 Solenoid valve kit⇔indoor unit tubes <2-tube side>
Indoor unit
Tubing size (mm)
(7) Plumbing separately purchased goods
● Gas Cut-off Valve Kit (for 2-WAY multi)
・ SGP-VK32K
The gas cut-off valve kit is installed in the refrigerant
gas tubes (largest tube) between the main tube and
outdoor units, as shown in Fig. 7.
* If a vibration-resistant frame is to be used, refer to
the chapter, using a Vibration-Resistant Frame.
●Solenoid Valve Kit (for 3-WAY multi)
・ ATK-RZP56BGB
・ ATK-RZP160BGB
① Install the solenoid valve kit at a point within 30 m
of the indoor unit.
② For places where quiet is an important
consideration, such as hospitals, libraries, hotels,
etc., we recommend installing the solenoid valve
kit away from rooms, such as in the ceilings of
hallways, to avoid annoyance due to refrigerant
noise.
③ Install an inspection port near the solenoid valve
kit so it can be serviced.
35.6 to 142.0 28.1 to 35.5 16.1 to 28.0
Ø28.58
Ø28.58
(Ø31.75)
(Ø31.75)
Ø22.22
Ø22.22
Ø19.05
Ø15.88
Ø28.58
Ø28.58
(Ø31.75)
(Ø31.75)
Ø25.4
Ø25.4
Ø19.05
Ø19.05
Ø28.58
Ø28.58
(Ø31.75)
(Ø31.75)
Ø25.4
Ø25.4
Ø19.05
Ø19.05
Suction tube
Discharge tube
Liquid tube
Unit Type
Equivalent Horsepower
Gas tube
Liquid tube
Post-branch main tubing
Total capacity for connected indoor units (kW)
Ø28.58
Ø25.4
Ø22.22
Ø19.05
Ø15.88
Ø12.7
Ø28.58
Ø25.4
Ø22.22
Ø19.05
Ø15.88
Ø12.7
Ø28.58
Ø25.4
Ø22.22
Ø19.05
Ø15.88
Ø12.7
Ø15.88
Ø12.7
Ø9.52
22-56 kW
0.8-2.0
Ø12.7
Ø6.35
Line anchor point
Main tube
Liquid tube (small tube)
Gas tube (largest tube)
Gas Cut-off Valve Kit
SGP-VK32K (sold separately)
Room
Room
Indoor unit
Indoor unit
Solenoid valve kit
Hallway
EN - 8
9.0 to 16.0
Under 9.0
Ø19.05
Ø15.88
Ø15.88
Ø12.7
Ø9.52
Ø9.52
Ø19.05
Ø15.88
Ø15.88
Ø12.7
Ø9.52
Ø9.52
Ø19.05
Ø15.88
Ø15.88
Ø12.7
Ø9.52
Ø9.52
71-160 kW
2.5-6.0
Ø15.88
Ø9.52
Tubing anchor
Fig. 7
Room
Room
Indoor unit
Indoor unit
Solenoid valve kit
Hallway
Fig. 8